3.8.8
Reclose Relay Test Menu
This menu permits the setting and testing of a reclose relay. These tests should be conducted in
accordance with the manufacturers relay specifications.
Figure 74 Reclosing Relay Test Menu Screen
There are several options to further define the tests to be performed. Selecting one of these
options will present the test setup screen for that option.
For electronic relays, apply a current, get a relay trip and record the trip time, remove the current,
toggle the 52a & 52b contacts (Binary Outputs 1 & 2), monitor the reclose contact, toggle the 52a
& 52b contacts again, apply current again, and look for lockout. This will be repeated for the total
number of operations selected in the setup screen.
For electro-mechanical relays, set the current to zero (trip curve will be ignored), set the number
of operations and reclose time, set a current, measure the trip and reclose time, and simulate the
52a & 52b contacts. This will be repeated for the total number of operations selected in the setup
screen.
The bottom of the screen has common buttons.
File:
This selection will take the user to the File
Manager.
Pre-set Test Menu:
This selection will return the controller to the
Pre-set Test Menu Screen.
Main Menu:
This selection will return the controller to the
Main Menu:
-