3.8.9.1 Frequency Relay Setting Screen
Figure 90 Frequency Relay Setting Screen
•
The Timing Settings button will change screens and will allow changes to meet the
manufacturer specifications.
•
The Target & Seal-In Settings button will change screens and will allow changes to meet the
manufacturer specifications.
•
The Pickup Settings button will change screens and will allow changes to meet the
manufacturer specifications.
•
Relay Tap, Time Dial, Normal Voltage, Normal Frequency, Reset Time, Target Tap, Fault
Frequency, and Trip Time to be set unless factory defaults are used.
•
The Timer Setup screen allows the user to define how the time will be used.
•
The relay will require a fault frequency and trip time to calculate the relay theoretical reclose.
The measurement is the delta frequency divided by the delta time where the setting can be
either a ramp rate or a step function as selected.
•
For electro-mechanical relays, a single set point, time dial, and a step function are required.
•
For the solid state relay, multiple set points may be used in conjunction with multiple times
plus a step or ramp function.
•
The step function or ramp rate may be single or double and the use of step / ramp may be
commingled.
The bottom of the screen has common buttons.
File:
This selection will take the user to the File
Manager.
Test Menu:
This selection will return the controller to the
Test Menu Screen.
Main Menu:
This selection will return the controller to the
Main Menu:
-