The bottom of the screen has common buttons.
File:
This selection will take the user to the File
Manager.
Batt Sim Off / Batt Sim On:
This selection will turn the Battery Simulator On
and Off.
Test Menu:
This selection will return the controller to the
Test Menu Screen.
Main Menu:
This selection will return the controller to the
Main Menu:
Start / Stop:
This selection will apply the set quantities
displayed and begin the test. After Start is
pressed this button will turn red and display
Stop. Pressing Stop at any time will stop the
test and turn the outputs off.
3.8.2.3 Impedance Relay Pre-fault Setting Screen
This screen sets the relay values before fault values are applied to ensure the relay is properly
energized.
Figure 33 Pre-Fault Setting Screen
•
The voltage range is 0.00 to 150.0 volts. This value may be set to two decimal places (i.e.
69.28) with a pull down menu that provide values of 57.735, 63.51, 69.28, 110.0 and 120.0
volts.
•
The voltage can be set phase-to-neutral (
φ
-N) or phase-to-phase (
φ
-
φ
) with a factory default
voltage of 69.28
φ
-N.
•
The current range is 0.00 to 9.99 amps with the factory default setting of 3.00 amps.
•
There are two parts to defining the angle. The first part is set in the System Default Screen
where the angle entry is defined as leading or lagging. Lagging value range is 0
°
to 360
°
,
53