Technical Manual
Glass Push Button II Smart & Push Button Smart 86
MDT technologies GmbH, Geschäftsbereich Gebäudeautomation
Phone: +49-2263-880
•
Fax: +49-2263-4588
•
E-Mail: [email protected]
•
www.mdt.de
55
55
Presentation:
With the button function "switching short/long", the function of the short button or the function of
the long button can be displayed. The displayed settings depend on whether the function to be
displayed has been parameterized as "switch" (switch, switch on, switch off, toggle) or "send values".
If the function has been parameterized as "
switch
", the following presentation settings are possible:
The switching function can display the two possible states (On/Off) by freely selectable symbols with
a freely selectable color. The evaluated status is visualized:
Figure 35: Presentation – Switch function
If the function has been parameterized as "
Send values
", the following settings are possible:
The presentation of the function "send values" depends on the selected datapoint type. Depending
on the selected datapoint type, 1-4 different symbols and their color can be selected.
The following table provides an overview of the settings for the various datapoint types:
Datapoint type
Adjustable symbols
Comment
2 Bit Switch control, DPT 2.001
4 symbols can be set: 1 symbol
for each possible state
1 Byte Percent, DPT 5.001
Three icons can be set for the
ranges 0%, 1% - 90% and > 90%.
Therefore the button evaluates
the information of the "Status
for display" object
Special presentation possible!
Additionally it is possible to
display the status value below
the symbol.
1 Byte Decimal factor, DPT
5.005
3 symbols can be set for the
ranges 0, 1-229 and 230-255.
Therefore, the button evaluates
the information of the "Status
for display" object
Special presentation possible!
Additionally it is possible to
display the status value below
the symbol.
1 Byte Scene Number, DPT
17.001
1 fixed symbol can be set
2 Byte Color temperature
(Kelvin), DPT 7.600
1 fixed symbol can be set
2 Byte Temperature, DPT 9.001
1 fixed symbol can be set
Special presentation possible!
2 Byte Brightness, DPT 9.004
1 fixed symbol can be set
3 Byte RGB Wert, DPT 232.600
1 fixed symbol can be set
Table 44: Presentation (Symbols) – Send values