4.6.2.1 Submenu – Logic 1-4
A submenu is activated for each activated logic. Up to 2 external logic objects and up to two buttons
can be integrated into the logic operation.
The following figure shows the corresponding settings:
Figure 54: Settings – Submenu: Logic 1-4
The table below shows all available settings:
ETS-Text
Dynamic range
[Default value]
Comment
Logical object 1 A/B
(external)
disabled
normal active, with
preallocation 0
inverted active, with
preallocation 0
normal active, with
preallocation 1
inverted active, with
preallocation 1
Activation of the external logic
object.
The preallocation value defines
the value of the external logic
object after a bus voltage recovery
if no value has yet been sent to the
communication object
Internal Input 1/2
disabled
Push Button 1-12
Activation of the buttons for the
logic function, each button can be
activated normally or inverted
Push button 1-12
disabled
normally active
inverted active
Each button can be activated
normally or inverted
Figure 55: Settings – Submenu: Logic 1-4
Depending on the activated inputs of the logic operations, the corresponding communication objects
are displayed:
Number
Name
Length
Usage
65
Logic – Input 1 A
1 Bit
external input for the logic function
66
Logic – Input 1 B
1 Bit
external input for the logic function
Table 77: Communication objects – Inputs Logic 1-4
For each external logic input, a communication object is shown, which can be connected to any other
communication object of the size 1 bit, e.g. the status of an actuator. Further, the logic operation can
respond to the operation of the keys. Each logic input can be either normal or inverted.