11.0
SCREEN DEFINITIONS, ALPHABETICAL LIST
www.maxcessintl.com
MAGPOWR Spyder-Plus-S1 Tension Control
MI 850A351 1 C
Page 50 of 68
Dancer Input
Pos Setpoint
From
Cal Dancer
menu.
Used to select whether the Dancer Input or the Position Setpoint
input will be calibrated.
Derivative Time
From the
Parameters
menu
Set the derivative time. Derivative time is only used for Control Type
Dancer, Torque
. See Section 9.6.6 for defaults.
Error Limit
From the
Parameters
menu.
Enter a value for the error limit between 10% and 100%. The error
limit aids the tuning process by setting a boundary for the actual
tension/position error that the Spyder will recognize during control
corrections. Smaller values for the error limit will lengthen the amount
of time necessary for Spyder to correct large tension/position
transients. The factory default is 100%.
First I at Full. Then P at core
From the
Tuning
menu for Unwinds and Rewinds.
Selects which parameter to optimize.
The Spyder should be optimized at or near full roll first. On rewinds
“Quick Stab” may be needed while a full roll is wound.
The Spyder should be optimized at core only after it has been
optimized at full roll.
On unwinds “Quick Stab” may be needed to
keep the system stable while an initial roll is unwound.
See tuning procedure in section 6.4 or 7.5.
First P at Full. Then Mc at core.
From the Tuning menu for Dancer, Torque, with Diameter systems.
Selects which parameter to optimize.
See tuning procedure in section 7.6
FTP Address
From the
Network
menu.
Enter the address of the FTP site that will be used to obtain Spyder
update programs.
Full Roll Diameter
From the
Taper Setup
menu for load cell system and the
Parameter
menu for Dancer Torque and Open Loop Tension systems. Enter the
value of the diameter of the full roll.
From the Inertia Setup menu for load cell system. Enter the full roll
diameter of the roll used in inertia setup.
Full roll tuning is optimal
From the
Tuning
menu for unwinds and rewinds.
This screen announces that Integrator Time has been decreased to
the minimum allowed during tuning (0.01 seconds). Integrator Time
can be set lower than this using the Parameters menu, but that is not
recommended.
Gateway Address
From the
Network
menu.
Enter the IP address of the gateway. The gateway is normally your
router. If DHCP is enabled this address is ignored. This address is
only needed if access to the world wide web is needed for updating
the Spyder program.
Hold Level
From the
Parameters
menu.
The output level of the Spyder will go to this value in Hold Mode. The
Spyder switches to Hold Mode when the Run/Stop Input is opened.
Hold Mode only occurs in while in Auto. Hold mode is delayed Stop
Time seconds after the Run/Stop input is opened.