13.0
RESET FUNCTIONS
www.maxcessintl.com
MAGPOWR Spyder-Plus-S1 Tension Control
MI 850A351 1 C
Page 67 of 68
The Spyder has functions that are activated by holding down keys while turning on power.
13.1
Automatic Contrast Adjust
The automatic contrast adjustment is activated by holding down the
and
keys while turning on
the power. Hold the keys for at least 6 seconds after power is on. The display will repeatedly sweep
through the full contrast range until the
key is pressed. When the display is readable, press the
key to exit contrast adjustment.
13.2
Reset All Parameters Except Calibrations to Defaults
All parameters except calibrations will be reset to defaults by holding down the
and
keys while
turning on the power. Hold the keys until the screen shows
"Resetting Parameters"
.
13.3
Reset All Parameters to Defaults (Including Calibrations)
All parameters will be reset to defaults by holding down the
and
keys while turning on the
power. Hold the keys for at least 6 seconds after power is on. This reset will erase all calibrations.
See Section 7.3, 7.4, or 8.4 for recalibrating inputs, Section 9.4 for recalibrating outputs, Section 6.3
for recalibrating load cells, Section 13.1 for setting contrast, and Section 6.4 or 7.5 for tuning the
Spyder.
WARNING: THIS RESET WILL ERASE ALL CALIBRATIONS.
13.4
Download Software
To download new software hold down the
and
keys while turning on power and hold the keys
until the display shows
"Update Software"
. See Section 12.4 for software updating.