11.0
SCREEN DEFINITIONS, ALPHABETICAL LIST
www.maxcessintl.com
MAGPOWR Spyder-Plus-S1 Tension Control
MI 850A351 1 C
Page 55 of 68
Setpoint Position
In the
Operator Loop
.
For dancer with Setpoint = Analog this is only a display of the current
setpoint input between Term.16 and Term.17.
For dancer with Setpoint = Ethernet the position setpoint may be
entered on this screen by pressing the ENTER key or using the LEFT
and RIGHT keys to increment and decrement the position.
Setpoint Source
In the
Configure
menu.
Selects the setpoint source for either Tension or Position. The choice
is either Analog or Ethernet. The Spyder defaults to Analog input as
the setpoint source.
Signal too low at Max Tension
From the
Cal Sensors
menu.
The Spyder will not calibrate if the loading of the load cells at
Maximum Tension is less than 1/8 of the load cell rating.
Start Time
From the
Parameters
menu.
Enter a value based upon the amount of time it takes your machine to
ramp up from stopped to steady state operation. If the tension spikes
during this time, try increasing this START TIME value.
Stop Multiplier
From the
Parameters
menu.
Enter a value that will dictate the control output during STOP mode.
Spyder will use the last control output sent during RUN mode before
the STOP signal is received and multiply it by the value set here for
the duration of the Stop Time. The control continues to control
tension during the Stop Time. When the stop multiplier value is
correctly set, it will automatically boost output to the braking device
during stops to keep the tension constant.
Stop Time
From the
Parameters
menu.
Enter a value based upon the amount of time it takes your machine to
ramp down from steady state operation to a complete stop. When this
time has expired, Spyder will automatically proceed into HOLD mode.
Stop Torque Ratio
From the
Parameters
menu.
Enter a value which increases the response of a Dancer, Torque with
Diameter system near core. Too low a value could cause poor
position control at core. Too high a value could cause diameters near
full roll to oscillate.
Subnet Mask
From the
Network
menu.
Determines the range of addresses in a subnet. Consult your system
administrator. If DHCP is enabled this parameter is ignored.
Switch to Quick Stab
From the
Tuning
menu.
When a tuning parameter is adjusted to its most stable value and the
system is still unstable, the Spyder automatically switches to Quick
Stab so that the other parameters are tuned in the correct order.