11.0
SCREEN DEFINITIONS, ALPHABETICAL LIST
www.maxcessintl.com
MAGPOWR Spyder-Plus-S1 Tension Control
MI 850A351 1 C
Page 52 of 68
Load very small. Maybe shorted.
From the
Cal Sensors
menu.
This is a warning message during load cell calibration. See
Load Cell
Calibration Problems
in Section 10.4.
Manual Level
In the
Operator Loop
.
When Manual Mode is selected by the Auto/Manual input (Term.12)
the Spyder control output is determined solely by the Manual Level
input Term.20 to Term.21. This value is display only.
Maximum Tension
From
Cal Sensors
menu.
Enter a value to set the upper limit of the tension range as read by
the load cells. You should choose a value for the max tension that will
have room for the highest setpoint tension you plan to run plus any
tension errors that may occur during operation within limits of the load
cell load rating. This setting also determines the scale for the analog
displays.
Maximum Velocity
From the Parameters menu for load cell. Sets the maximum line
speed velocity for use in the inertia compensation calculation.
Meter 100% CAL
From the
Recal Outputs
menu.
Used to calibrate the tension meter output (Term.33 to
Term.34).when the tension is at Maximum Tension.
Modbus Address
From the
Network
menu.
Sets the Modbus address of this Spyder.
Modbus Byte Order
From the
Network
menu.
Determines whether Modbus data is sent with the most significant
byte first or last.
Modbus Word Order
From the
Network
menu.
Determines whether Modbus data is sent with the most significant
word first or last.
Network
One of the top level menu screens. Used to set IP addresses, and
other network parameters.
Numeric Rate
From the
Configure
menu.
Use to adjust the update and filter rate of the numeric displays of
tension/position and output.
Operator Loop
One of the top level menu screens. All screens in this menu are
display only except for Taper Percent. This menu provides numeric
and bar graph displays of setpoint and actual tension, position and
output level.
This is the default entry point for all operator displays.
Out of range at Max Tension
Error message during load cell calibration. See
Load Cell Calibration
Problems
in Section 10.4.
Out of Range at Max Tension
From the
Cal Sensors
menu.
See
Load Cell Calibration Problems
in Section 10.4.
Output 0% CAL
From the
Recal Outputs
menu.
Used to calibrate the control output (Term.30 to Term.31) when 0%
output is commanded.