11.0
SCREEN DEFINITIONS, ALPHABETICAL LIST
www.maxcessintl.com
MAGPOWR Spyder-Plus-S1 Tension Control
MI 850A351 1 C
Page 53 of 68
Output 100% CAL
From the
Recal Outputs
menu.
Used to calibrate the control output (Term.30 to Term.31) when 100%
output is commanded.
Output Level
In the
Operator Loop
Actively displays the present output (Term.30 to Term.31) of the
Spyder.
Parameters
One of the top level menu screens. Used to change parameters such
as Proportional Gain, Integrator Time, Error Limit, Start Time, Stop
Time, Stop Multiplier, and Hold Level.
Preferences
One of the top level menu screens. Used to select Language
(English, Francais, Deutsche, Italiano, Espanol), Tension Units(lb, oz,
Kg, N, g, ), and Distance Units (in, ft, mm, cm, m)
Present Dia
In the
Taper Setup
menu for load cell system. Used to calibrate the
diameter for use in taper tension. Displays the diameter if diameter
has been calibrated.
In
Cal Diameter
menu for Dancer and Open loop tension system.
Used to calibrate the diameter. Diameter calibration is required.
Also shows in the
Operator Loop
menu.
Primary tuning is optimal
From the
Tuning
menu for point to point systems.
This screen announces that Integrator Time has been decreased to
the minimum allowed during tuning (0.01 seconds). Integrator Time
can be set lower than this using the Parameters menu, but that is not
recommended.
Program Number
From the
Network
menu.
The number of the program that will be downloaded from the FTP site
to update the Spyder software.
Proportional Gain
From the
Parameters
menu.
Enter a value for the proportional gain. This tuning parameter adds a
correction factor that is proportional to the deviation from the tension
setpoint. A higher value will make the system more responsive but a
proportional gain that is too high will result in an unstable system.
Factory default setting is 0 for load cell systems and 1.0 for dancer
systems.
Quick Stab
One of the top level menu screens. Used to quickly stabilize an
unstable system. After stabilizing, the system should be tuned using
the Tuning menu.
Recal Inputs
One of the top level menu screens. Used to recalibrate the Tension
setpoint input (Term.16 to Term.17) and the Manual setpoint input
(Term.20 to Term.21).
Recal Outputs
One of the top level menu screens. Used to recalibrate the control
output and the tension meter output.
Retune I now, then retune P
Part of
Quick Stabilize
on point to point systems. This screen
appears when Quick Stabilize has stabilized the system while I is
being adjusted. Immediately retune I. When I is optimum retune P.
Retune I now. Then P at core.
Part of
Quick Stabilize
on unwinds or on rewinds. This screen
appears when Quick Stabilize has stabilized the system while I is
being adjusted. Retune the system at the present diameter and then
retune P when the system is again at core.