8 Commissioning
Maschinenfabrik Reinhausen GmbH 2022
74
8595017/00 EN
TAPCON
®
250
NOTICE
Damage to the device!
A dielectric test with a test voltage that is greater than the maximum permit-
ted test voltage can lead to the device being damaged.
► Perform the dielectric test with a test voltage that is less than or equal to
the maximum permitted test voltage.
► Perform the dielectric test using the permitted interfaces only.
Depending on the device configuration, you may only test the assemblies
listed below. You may not test any other assemblies.
Assembly
Interfaces
Test parameters
Max. test voltage
Max. test dura-
tion
Ramp
Breaking current
threshold
AI-8340
X2-9 to 8
X2-7 to 6
X2-5 to 4
2.0 kV AC
2 s
5 s
> 4 mA
DO-8212
DO
2.0 kV AC
2 s
5 s
> 1 mA
G1 (PULS) and G2 N, L
2.0 kV AC
2 s
5 s
> 4 mA
Table 13: Permitted interfaces and test parameters for the dielectric test