9 Operation
Maschinenfabrik Reinhausen GmbH 2022
98
8595017/00 EN
TAPCON
®
250
Option
Description
Parameter list
Parameter list with descriptive text and values (min, max, cur-
rent).
Event list
Complete list of all possible events.
Operating in-
structions
Operating Instructions.
Settings
Configuration of parameters and events.
Security log
Logbook of all instances of access and changes relating to secu-
rity.
Licenses
Copyright and disclaimers of the software components
used.
Table 22: Exporting data
1. Go to
Settings > Export
.
2. Select the desired option for the export.
9.1.14.2 Importing data
You can import the following data:
Option
Description
System image
Complete image of the system (software and configura-
tion), with or without history.
Settings
All device settings:
▪ Parameter settings
▪ Event settings
▪ Administrative settings (users, access rights)
The settings can also be imported from another device.
SSL certificate
Import of an SSL certificate with associated key:
▪ Server certificate (.crt + .pem)
▪ Client certificate (.crt + .pem)
▪ Client CA (.crt)
To import your own certificate, the certificate must contain
the IP address 192.168.166.1 in the Subject Alternative
Name (SAN) to avoid error messages on the display.
For the import, you will have to compress the certificate
(*.crt) and key (*.pem) in a zip file.
You can import certificates with the following key authenti-
cation:
▪ RSA with 1024 bits
▪ ECDSA with 256 bits ("secp256r1" or "prime256v1"
curve).
Table 23: Importing data