9 Operation
Maschinenfabrik Reinhausen GmbH 2022
85
8595017/00 EN
TAPCON
®
250
The digital inputs available are each permanently linked to a
General pur-
pose input
event message for this purpose.
Input/command
Event message
Digital input 1
General purpose input 1
Digital input 2
General purpose input 2
...
...
Table 18: Links between digital inputs and event messages
You can link the event messages with device functions and digital outputs.
You can also link all other event messages (e.g.,
Undervoltage U<
) with digi-
tal outputs. Corresponding parameters, for which you need to enter the rele-
vant event number, are provided for this purpose.
9.1.7.1 Linking functions
You can link the
General purpose input
events with device functions. This al-
lows you to control the device remotely via digital inputs.
To establish the link, you have to enter the corresponding event number in
the desired parameter.
Note that you can only enter the event numbers of the
General purpose in-
put
events.
If you enter event number 500, the link is disabled.
ü
The desired event number is known.
1. Go to
Settings > Parameters > System > Link functions
.
2. Select the desired parameter.
3. Enter the desired event number.
4. Press the
Accept
button to save the modified parameter.
Local/Remote
The assigned event activates LOCAL or REMOTE mode on the device.
Blocking
If the assigned event is active, automatic control is blocked.
Independent regulation
If the assigned event is active, the device activates the independent regula-
tion independent mode.