Screensaver waiting time
You can use this parameter to set the screensaver waiting time.
9.1.5 Configuring syslog
The device supports the transmission of log messages via the syslog proto-
col in accordance with the following standards
▪ RFC 5425
▪ RFC 3164
▪ RFC 5426
▪ RFC 6587
1. Go to
Settings > Parameters > System > Syslog
.
2. Select the desired parameter.
3. Set the parameter.
4. Press the
Accept
button to save the modified parameter.
Activate syslog
You can use this parameter to activate transmission of syslog messages via
the device.
Syslog standard
You can use this parameter to adjust the transmission process and the for-
mat for the syslog messages. You can select the following options:
Standard
Transport
Message format
RFC 5425 (recom-
mended)
TLS
RFC 5424
RFC 5426
UDP
RFC 6587
TCP
RFC 3164
UDP
RFC 3164
Table 16: Syslog standard
If you use the standard RFC 5245 (TLS), you have to import the root certifi-
cate and the client certificate with the corresponding key to the syslog
server. For more information, refer to the section titled Importing data.
Syslog server
You can use this parameter to set the IP address of the syslog server.