9 Operation
Maschinenfabrik Reinhausen GmbH 2022
91
8595017/00 EN
TAPCON
®
250
Description
O: Lower
If a signal is present at the input, the de-
vice activates the LOWER function.
O: Raise
If a signal is present at the input, the de-
vice activates the RAISE function.
O: TDSC® active
If a signal is present at the input, the de-
vice activates the TDSC® function.
9.1.7.4 Linking digital outputs
You can link each event with a digital output. The device provides 5 digital
outputs (GPO) for this purpose. When you link a digital output to an event,
the device issues a signal to this output if the event occurs. The signal per-
sists until the event stops. A parameter is available for each available digital
output.
To forward input signals, you need to link the digital outputs with the
Gen-
eral purpose input
events.
ü
The desired event number is known.
1. Go to
Settings > Parameters > System > Link outputs
.
2. Select the desired parameter.
3. Enter the desired event number.
4. Press the
Accept
button to save the modified parameter.
Generic digital output X
You can use this parameter to link the digital output with an event message.
To do so, enter the desired event number.
If you enter event number 500, the link is disabled.
9.1.8 Configuring analog inputs
You can flexibly configure the device's analog inputs and assign device
functions.
The device supports analog sensors with linear characteristic curves and
only outputs analog signals with linear characteristic curves.