9 Operation
Maschinenfabrik Reinhausen GmbH 2022
105
8595017/00 EN
TAPCON
®
250
If you use this circuit, set the device as follows:
Parameter
Option
Voltage-transformer circuit
3 Ph differential voltage
Current-transformer circuit
3 Ph total current
Phase angle correction
0°
Table 28: Circuit 1-C
Circuit 1-D
L1
L2
L3
U
L1
VT
CT
U
L1
I
L1
I
L2
I
L3
U
L3
U
L2
U
L1
-U
L2
-U
L2
I
L3
UI
L
N
k
l
Figure 61: Circuit 1-D
▪ The voltage transformer VT is connected to the phase conductors L1 and
L2.
▪ The current transformer CT is looped into the phase conductor L3.
▪ The current I
L3
is ahead of voltage U
L1
-U
L2
by 90°. This corresponds to a
phase shift of -90°.
▪ The voltage drop on a phase conductor is determined by the current I
L3
.
If you use this circuit, set the device as follows:
Parameter
Option
Voltage-transformer circuit
3 Ph differential voltage
Current-transformer circuit
3 Ph phase current
Phase angle correction
90°
Table 29: Circuit 1-D