9 Operation
Maschinenfabrik Reinhausen GmbH 2022
77
8595017/00 EN
TAPCON
®
250
9 Operation
This chapter describes all the functions and setting options for the device.
9.1 System
9.1.1 General
You can set general parameters in this menu item.
9.1.1.1 Setting general device functions
You can set general device functions with the following parameters.
1. Go to
Settings > Parameters > System > General
.
2. Select the desired parameter.
3. Set the parameter.
4. Press the
Accept
button to save the modified parameter.
Commissioning wizard
You can use this parameter to set whether the commissioning wizard is to
launch automatically when the device is restarted.
Measured value display
You can use this parameter to set whether the displayed measured values
and control parameters are to refer to the primary side or secondary side of
the measuring transducers.
Transformer name
You can use this parameter to enter a transformer name for identification
purposes. The transformer name will be displayed on the main screen in the
visualization.
9.1.1.2 Set up automatic logout
You can change the settings so that the device of a logged-in user automati-
cally logs the user out after a certain period of inactivity.
These settings apply to all users. If you have activated the Auto login func-
tion for a user, then this user will not be automatically logged out.
1. Go to
Settings > Parameters > System > General
.
2. Select the desired parameter.