9 Operation
Maschinenfabrik Reinhausen GmbH 2022
130
8595017/00 EN
TAPCON
®
250
If the value is above or below the set bandwidth, the
Function monitoring
event is displayed after the set delay time for function monitoring has
elapsed. The event is automatically acknowledged as soon as the measured
value is back within the set bandwidth.
The following parameters are available for setting function monitoring:
▪ Function monitoring
▪ Hysteresis
▪ Delay time
1. Go to
Settings > Parameters > On-load tap-changer regulator > U
bandwidth monitoring
.
2. Select the desired parameter.
3. Set the desired parameter.
4. Press the
Accept
button to save the modified parameter.
You can set additional parameters for each limit value:
Function monitoring
You can use this parameter to activate function monitoring. When doing so,
also observe the monitoring settings [
You can select the following options:
Setting
Behavior
Off
Function monitoring is deactivated.
Only Auto
Function monitoring is only active in AVR AUTO oper-
ating mode.
Auto and Manual
Function monitoring is active in AVR AUTO and AVR
MANUAL operating modes
Table 39: Activate function monitoring
Hysteresis
You can use this parameter to set the hysteresis. You can use this to avoid
the unnecessary generation of messages if the measured value fluctuates
around a threshold value.
Delay time
You can use this parameter to set the delay time in order to delay the issuing
of the event message.