9 Operation
Maschinenfabrik Reinhausen GmbH 2022
140
8595017/00 EN
TAPCON
®
250
Figure 78: U bandwidth monitoring
1. Go to
Settings > Parameters > On-load tap-changer regulator > U
bandwidth monitoring
.
2. Select the desired parameter.
3. Set the desired parameter.
4. Press the
Accept
button to save the modified parameter.
Also refer to
2
Function monitoring
You can use this parameter to activate function monitoring. When doing so,
also observe the monitoring settings [
You can select the following options:
Setting
Behavior
Off
Function monitoring is deactivated.
Only Auto
Function monitoring is only active in AVR AUTO oper-
ating mode.
Auto and Manual
Function monitoring is active in AVR AUTO and AVR
MANUAL operating modes
Table 41: Activate function monitoring
Hysteresis
You can use this parameter to set the hysteresis. You can use this to avoid
the unnecessary generation of messages if the measured value fluctuates
around a threshold value.