9 Operation
Maschinenfabrik Reinhausen GmbH 2022
83
8595017/00 EN
TAPCON
®
250
Syslog server port
You can use this parameter to set the port of the syslog server.
Reconnect delay time
You can use this parameter to determine how long the device will wait be-
fore it attempts to reconnect after the connection has been interrupted earlier
or a syslog message could not be transmitted (only for TCP or TLS).
Device designation
You can use this parameter to set the device designation that the device will
be identified with on the syslog server.
Severity level
You can set which syslog messages the device will send. You can also acti-
vate or deactivate messages for each severity level.
Severity level
Description
Emergency
The system is unusable.
Alert
Immediate intervention required.
Critical
Critical state
Error
Error state
Warning
Warning state
Notice
Notice state
Info
Information state
Debug
Debug state
Table 17: Severity levels
9.1.6 Setting the measured value recorder
Depending on the set average value interval, the measured value recorder
can display the measured values over a shorter or longer time period:
▪ Average value interval = 1 s: approx. 1 day and 8 hours
▪ Average value interval = 86,400 s (= 24 h): approx. 315 years