9 Operation
Maschinenfabrik Reinhausen GmbH 2022
78
8595017/00 EN
TAPCON
®
250
3. Set the parameter.
4. Press the
Accept
button to save the modified parameter.
Auto logout
You can use this parameter to activate th automatic logout function.
Time until auto logout
You can use this parameter to set the time period of inactivity after which a
user is automatically logged out.
9.1.1.3 Activating/deactivating service user access
The device is equipped with user access for the Maschinenfabrik Rein-
hausen GmbH Technical Service department. This access is for error diag-
nostics and troubleshooting in the event of device faults.
You can use this parameter to activate or deactivate service user access. To
safeguard IT security, only activate service user access for a limited time pe-
riod for remedying faults.
If you deactivate the service user access and lose your password for the ad-
ministrator role, it is not possible to reset the administrator password. If the
administrator password is lost, the device must be reset to the default set-
tings. When doing so, all information stored on the device (parameters,
measured values, etc.) will be lost.
You must be assigned the administrator role to set parameters.
When in delivery status, you can log in as the administrator as follows:
▪ User name:
admin
▪ Password:
admin
1. Go to
Settings > Parameters > System > General > Service user ac-
cess activation
.
2. Select the desired option.
3. Press the
Accept
button to save the modified parameter.
4. Restart the device to adopt the change.
Service user access activation
You can use this parameter to activate or deactivate service user access.