6 Mounting
Maschinenfabrik Reinhausen GmbH 2022
61
8595017/00 EN
TAPCON
®
250
Miniature circuit breaker
Safety fuse
Characteristics
B, C, K or Z
Fast-acting, medium-act-
ing or delayed-acting
Rated switching capacity
50 kA
For installation in accordance with IEC 61010-2-30
CAT II: 10 kA
Table 11: Permissible fuse types
1. Voltage measurement: Feed the wires into the terminals in accordance
with the connection diagram and fasten them using a screwdriver.
2. Current measurement: Feed the wires into the terminals in accordance
with the connection diagram and fasten them using a screwdriver.
6.4.6 Wiring the MC 2-2/SW3-3 assembly
1. Insert the supplied SFP module into the corresponding Ethernet interface
in accordance with the connection diagram and fold the clasp
down.
Figure 45: Engaging the SFP module