13 Technical data
Maschinenfabrik Reinhausen GmbH 2022
167
8595017/00 EN
TAPCON
®
250
13.2.8 Digital outputs DO 8
DO 8
Outputs (plug-based electrical isola-
tion)
8 relays
4 groups per module
Switching voltage
DC: 24 V, 48 V, 60 V, 110 V
AC: 110 V
Contact load capacity
Min.: 5 V DC, 10 mA
Max. DC: See diagram
Max. AC: 150 V; 3 A (8 active outputs)
or 5 A (4 active outputs)
Table 71: DO 8 assembly technical data
10
20
30
40
50
100
V
300
0.1
0.2
0.5
1
2
5
10
20
A
U
I
Ohmic load
Figure 83: Contact load capacity of digital outputs with resistive load
CAUTION
Electric shock!
The outputs of the DO assembly have plug-based electrical isolation. A mix-
ture of voltage ranges (e.g. extra low voltage and low voltage) or various
phases within a plug can lower the protection against electric shock.
► Use the same voltage ranges within a plug.
► Use the same phase within a plug.