9 Operation
Maschinenfabrik Reinhausen GmbH 2022
144
8595017/00 EN
TAPCON
®
250
Switching pulse pause
You can use this parameter to set the switching pulse pause between 2
switching pulses. The device can only issue another switching pulse once
the switching pulse pause has elapsed.
9.5.1.2 Setting motor runtime monitoring
The motor-drive unit's runtime can be monitored by the device. This function
is used to identify motor-drive unit malfunctions during the tap-change oper-
ation and to trigger any actions needed.
Behavior
The motor-drive unit issues the
Motor-drive unit running
signal during the
tap-change operation. This signal is present until the tap-change operation is
complete. The device compares the duration of this signal with the set motor
runtime. If the set motor runtime is exceeded, the device triggers the follow-
ing actions:
1.
Motor runtime exceeded
event.
2. Pulse signal via
Trigger motor protective switch
output relay
Note that motor-drive units with pass-through positions or motor-drive units
without stepped switching behavior will run for longer under certain circum-
stances. Set a longer motor runtime for such units.
1. Go to
Settings > Parameters > Motor and control cabinet > Motor
control
.
2. Select the desired parameter.
3. Set the parameter.
4. Press the
Accept
button to save the modified parameter.
Motor runtime
You can use this parameter to set the motor runtime.
Motor runtime monitoring
You can use this parameter to activate or deactivate motor runtime monitor-
ing.
9.5.1.3 Setting the switching direction
You can set the switching direction of the motor-drive unit.
1. Go to
Settings > Parameters > Motor and control cabinet > Motor
control
.
2. Select the desired parameter.
3. Set the parameter.