Installing AC power
19
3.2 Installing AC power
DANGER! Read "
on page 4 before attempting to install
this product.
Electrical installation must be carried out by qualified professionals only.
For protection from dangerous electric shock, the luminaire must be
grounded (earthed). The AC power distribution system must be fitted with
current overload and ground-fault (earth-fault) circuit breakers as well as a
means to isolate luminaires from power and lock out power during service.
Important! Do not connect the Exterior 1200 Wash to an electrical dimmer
system. Doing so can damage the electronics.
See Figure 5 on page 17 for a schematic diagram of cable layout.
If there is a break or cut at any point in a cable (for example at a connection point), and if
this is exposed to water, moisture can be drawn up the inside of the cable due to the
vacuum effect of temperature fluctuations during operation. Ensure that the luminaire is
protected from the entry of water via the power cable by using IP65-rated connectors or
junction boxes, or by protecting connectors with weatherproof housings.
The Exterior 1200 Wash must be supplied with power via an electrical cable that is
adequately dimensioned for the current requirements and suitable for the installation
environment, particularly with regard to water, pollution, thermal and UV resistance. Use
Hypalon or neoprene rubber-jacket cable rated to 90° C (194° F) minimum. The conductor
size must be 1.5 mm
2
(16 AWG) minimum. Check that all power cables are in perfect
condition.
Exterior 1200 Wash specifications"
on page 78 for details of fuse rating and typical
current. If you require help in planning or dimensioning the power distribution system,
please contact your Martin Architectural supplier for assistance.
Electrical power installation consists of two steps:
1. Configuring for local AC power
2. Connecting to AC power.
3 . 2 . 1 C o n f i g u r i n g f o r l o c a l A C p o w e r
Before AC power is applied to the Exterior 1200 Wash for the first time (or if the AC power
voltage or frequency changes), the luminaire must be configured to accept the local power
voltage and frequency as described in this section.
The Exterior 1200 Wash can accept the following AC voltages and frequencies:
• 200 V, 208 V, 220 V, 230 V, 240 V, 250 V or 277 V at 50 or 60 Hz.
Operating at the incorrect power setting can result in overheating and damage to the
luminaire and lamp. If your local power voltage differs from the voltage settings listed here
and in the luminaire, contact your Martin Architectural supplier for assistance.
The luminaire must be configured to accept the local AC power frequency and voltage by
connecting the free ends of two jumper leads. The fixed end of each lead sits in an orange
terminal. The free end of each lead must be connected to the appropriate terminal on the
terminal block. Terminals are labelled.
Summary of Contents for Exterior 1200 Wash
Page 1: ...user manual Exterior 1200 Wash ...
Page 3: ...3 Section 1 Safety ...
Page 9: ...Section 2 Introduction ...
Page 12: ...12 Exterior 1200 Wash user manual ...
Page 13: ...Introduction to the Exterior 1200 Wash 13 Section 3 Installation ...
Page 25: ...Installing a data link 25 Section 4 General ...
Page 30: ...30 Exterior 1200 Wash user manual ...
Page 31: ...General 31 Section 5 Settings and configuration ...
Page 39: ...Luminaire settings 39 Section 6 Stand alone operation ...
Page 49: ...Stand alone operation 49 Section 7 DMX control ...
Page 54: ...54 Exterior 1200 Wash user manual ...
Page 55: ...DMX controller operation 55 Section 8 Service and accessories ...
Page 70: ...70 Exterior 1200 Wash user manual ...
Page 71: ...Accessories 71 Section 9 Reference ...
Page 82: ...Notes ...
Page 83: ......