Section 7 – Programming (Continued)
63
SW3 position 4 disables the time-out-timer. Turning SW3-8 “ON” disables the time-out-timer. If disabling
the transmitter time-out-timer, remember to also replace the receiver(s) EPROM(s) to disable the time-out-
timer in the receiver.
7-6.4.
Positions 5-7 Special Crane Control Configurations, 2-Speed Membrane Only. (Standard all
“OFF”).
The 10K12 2-Speed Membrane transmitter is available with special crane control configurations. These
options are switch configurable on the transmitter. Section 6. Wiring shows all the different crane
configurations and the switch positioning needed to achieve them. The standard transmitter comes with the
output standard output configuration.
For 2-speed special crane control configurations:
See Section 6.
Wiring and program SW3 respectively on the transmitter.
7-6.5.
Position 8 No function. (Keep turned “OFF”).
7-6.6.
Transmitter Programming SW4 Positions 1-2 Mode Enable. (All 2-speed configurations all
“OFF”).
Mode 0, SW4 1 turned “OFF” and SW4 2 turned “OFF”. From the factory the standard 2-Speed Membrane
Transmitter is configured this way. This mode in the Membrane Transmitter is for all 2-speed applications.
If the Membrane Transmitter has a 2-speed keypad SW4 must be set to all “OFF” positions.
7-6.7.
Single-Speed Modes 1-3. (The following three different single-speed modes are listed for
single-speed Membrane Transmitters only). See Section 7-6.9 for details.
Mode 1, SW4 1 turned “ON” and SW4 2 turned “OFF”. This configuration gives four-motor single-speed
with up to four auxiliaries. This configuration uses the single-speed keypad with two auxiliaries labeled P1
and P2.
Mode 2, SW4 1 turned “OFF” and SW4 2 turned “ON”. This configuration gives four-motor single-speed
with four auxiliaries. This configuration uses the single-speed keypad with four auxiliaries labeled Aux 1
through Aux 4.
Mode 3, SW4 1 turned “ON” and SW4 2 turned “ON”. Allows for 12 independent ON/OFF functions
(relays) per transmitter button pushed.