IMPULSE•G+ Mini Advanced Instruction Manual – March 2014
5-23
4. With Load Check disabled, lift the rated load a foot or two off the ground.
5. Set C05.01 equal to 09.
6. Press and hold the Hoist (up) command button on the pendant or radio for full speed operation
(60 Hz).
NOTE:
The Load Check set up process can be temporarily paused by lowering the load block to
the ground (suspended), then pressing and holding the Hoist (up) command button at full
speed until the Load Check set up process is complete.
7. When the Load Check set up process finishes its calculations, the drive will decelerate the load
to indicate that the set up calibration is complete (LC dn).
8. Press the Lower (down) command to complete the Load Check set up process.
9. Lift the rated load numerous times to ensure there are no unwanted LC alarms. If an LC alarm is
detected, increase the LC Margins (C5.05 and/or C5.07).
NOTE:
If an application requires Load Check to be bypassed, an MFDI may be programmed to
69.
NOTE:
If an error occurs during the Load Check set up, the load being lifted causes current or
torque to exceed 250%. Increase holding time and testing time, and decrease the load
weight.
Clearing a Load Check Alarm (LC) (V/f and OLV operation)
A Load Check alarm can be reset based on the setting of LC Alarm Action (C05.02).
When C05.02 = 1, 2, or 4:
Program H01.xx = 69 (LC Bypass), then cycle the MFDI to clear the
Load Check Alarm (LC).
NOTE:
Only lowering is allowed.
When C05.02 = 3:
Program H01.xx = 3F (Fault Reset), then cycle the MFDI to clear the Load
Check Alarm (LC).
NOTE:
Drive fault.
Parameter
Code
Name
Function
Range
Initial Value
Access
Level
C05.01
Load Check (LC)
Used to set up and enable the Load Check
function.
00, 01, 03,
09
00
Adv
00 Disable
01 Enable Load Check
03 Enable Load Check Continuous
09 Load Check Set Up
C05.02
LC Alarm Action
Sets the action at a Load Check alarm or
fault (Fault reset is required via keypad or
MFDI to raise the load).
00–04
04
Adv
00 Alarm Only (Continue operation)
01 Decel to Stop (Allows lower only)
02 Coast to Stop (Allows lower only)
03 Fault Stop (No operation)
04 Use B03.03 Method (allows lower
only)
Summary of Contents for 2001-G+M
Page 2: ......
Page 9: ...C h a p t e r 1 Introduction...
Page 10: ...IMPULSE G Mini Advanced Instruction Manual March 2014 1 2 This page intentionally left blank...
Page 16: ...IMPULSE G Mini Advanced Instruction Manual March 2014 1 8 This page intentionally left blank...
Page 17: ...C h a p t e r 2 Installation...
Page 18: ...IMPULSE G Mini Advanced Instruction Manual March 2014 2 2 This page intentionally left blank...
Page 25: ...C h a p t e r 3 Wiring...
Page 26: ...IMPULSE G Mini Advanced Instruction Manual March 2014 3 2 This page intentionally left blank...
Page 38: ...IMPULSE G Mini Advanced Instruction Manual March 2014 3 14 This page intentionally left blank...
Page 39: ...C h a p t e r 4 Getting Started...
Page 40: ...IMPULSE G Mini Advanced Instruction Manual March 2014 4 2 This page intentionally left blank...
Page 60: ...IMPULSE G Mini Advanced Instruction Manual March 2014 4 22 This page intentionally left blank...
Page 61: ...C h a p t e r 5 Programming Features...
Page 62: ...IMPULSE G Mini Advanced Instruction Manual March 2014 5 2 This page intentionally left blank...
Page 153: ...Troubleshooting IMPULSE G Mini C h a p t e r 6...
Page 154: ...IMPULSE G Mini Advanced Instruction Manual March 2014 6 2 This page intentionally left blank...
Page 165: ...IMPULSE G Mini Advanced Parameter Listing A p p e n d i x A...
Page 166: ...IMPULSE G Mini Advanced Instruction Manual March 2014 A 2 This page intentionally left blank...
Page 190: ...IMPULSE G Mini Advanced Instruction Manual March 2014 A 26 This page intentionally left blank...