IMPULSE•G+ Mini Advanced Instruction Manual – March 2014
5-73
Overtorque detection 2 functions the same as overtorque/undertorque detection 1 (
L06.01
), except
that “OT2/UT2” is displayed on the digital operator instead. This function is used when two types of
detection are output to the multi-function output terminals.
Parameter
Code
Name
Function
Range
Initial
Value
Access
Level
L06.02
Torque Detection 1 Level
Sets the overtorque detection as
a percentage of inverter rated
current, during V/f control, and
motor rated torque during vector
control.
0–300%
150
Basic/Adv
L06.03
Torque Detection 1 Time
The overtorque detection delay
time inserts a delay, between the
time motor current (or torque)
exceeds the overtorque level
(L06.02) and when the
overtorque detection function is
enabled. The digital operator
then displays “OT1”.
0.0–10.0 sec
0.1
Basic/Adv
L06.04
Torque Detection 2 Select
Activates overtorque/
undertorque detection, and
selects whether detection
generates an alarm or a fault.
00–08
00
Adv
00 Disable
Adv
01 Overtorque At Speed
Agree (Alarm)
Adv
02 Overtorque
At
Run
(Alarm)
Adv
03 Overtorque At Speed
Agree (Fault)
Adv
04 Overtorque At Run
(Fault)
Adv
05 UT At Speed Agree
(Alarm)
Adv
06 UT At Run (Alarm)
Adv
07 UT At Speed Agree
(Fault)
Adv
08 UT At Run (Fault)
Adv
Table 5-11: Torque Detection 1 Selection Definition
Setting
Description
00
Torque detection is disabled (
factory default
).
01
Overtorque detection is enabled whenever at the speed agree level (when inverter is not accelerating
or decelerating). Continue running after detection (OT1 alarm).
02
Overtorque detection is enabled always. Continue running after detection (OT1 alarm).
03
Overtorque detection is enabled whenever at the speed agree level. Coast to a stop after detection
(OT1 fault).
04
Overtorque detection is enabled always. Coast to a stop after detection (OT1 fault).
05
Undertorque detection is enabled whenever at the speed agree level (when inverter is not accelerating
or decelerating). Continue running after detection (UT1 alarm).
06
Undertorque detection is enabled always. Continuing running after detection (UT1 alarm).
07
Undertorque detection is enabled whenever at the speed agree level. Coast to a stop after detection
(UT1 fault).
08
Undertorque detection is enabled always. Coast to stop after detection (UT1 fault)
Summary of Contents for 2001-G+M
Page 2: ......
Page 9: ...C h a p t e r 1 Introduction...
Page 10: ...IMPULSE G Mini Advanced Instruction Manual March 2014 1 2 This page intentionally left blank...
Page 16: ...IMPULSE G Mini Advanced Instruction Manual March 2014 1 8 This page intentionally left blank...
Page 17: ...C h a p t e r 2 Installation...
Page 18: ...IMPULSE G Mini Advanced Instruction Manual March 2014 2 2 This page intentionally left blank...
Page 25: ...C h a p t e r 3 Wiring...
Page 26: ...IMPULSE G Mini Advanced Instruction Manual March 2014 3 2 This page intentionally left blank...
Page 38: ...IMPULSE G Mini Advanced Instruction Manual March 2014 3 14 This page intentionally left blank...
Page 39: ...C h a p t e r 4 Getting Started...
Page 40: ...IMPULSE G Mini Advanced Instruction Manual March 2014 4 2 This page intentionally left blank...
Page 60: ...IMPULSE G Mini Advanced Instruction Manual March 2014 4 22 This page intentionally left blank...
Page 61: ...C h a p t e r 5 Programming Features...
Page 62: ...IMPULSE G Mini Advanced Instruction Manual March 2014 5 2 This page intentionally left blank...
Page 153: ...Troubleshooting IMPULSE G Mini C h a p t e r 6...
Page 154: ...IMPULSE G Mini Advanced Instruction Manual March 2014 6 2 This page intentionally left blank...
Page 165: ...IMPULSE G Mini Advanced Parameter Listing A p p e n d i x A...
Page 166: ...IMPULSE G Mini Advanced Instruction Manual March 2014 A 2 This page intentionally left blank...
Page 190: ...IMPULSE G Mini Advanced Instruction Manual March 2014 A 26 This page intentionally left blank...