IMPULSE•G+ Mini Advanced Instruction Manual – March 2014
5-46
Terminal Parameters
There are both digital and analog inputs and outputs that can be programmed for customized
operation and sequencing. These include input and output terminal selection along with serial
communication. Listed below are the parameters in this section that are customizable for your
system.
•
H1 Digital Inputs
•
H2 Digital Outputs
•
H3 Analog Inputs
•
H4 Analog Outputs
•
H5 Serial Communication Set-up
•
H6 Pulse Inputs
Digital Inputs
The IMPULSE•G+ Mini has seven multi-function contact inputs for the set-up of numerous
functions. The following table lists the function selections for the multi-function contact inputs
(terminals S1 to S7) and indicates the control modes during which each function can be enabled. An
OPE03 error will occur if the same function is programmed in more than one terminal at the same
time.
Parameter
Code
Name
Function
Reference
Page
Number
Range
Initial
Value
Access
Level
H01.01
Terminal S1 Select
Selects the multi-function
inputs. Setting for S1.
--
00–81
80*
Basic/Adv
H01.02
Terminal S2 Select
Setting for S2.
--
00–81
81*
Basic/Adv
H01.03
Terminal S3 Select
Setting for S3.
--
00–81
00*
Basic/Adv
H01.04
Terminal S4 Select
Setting for S4.
--
00–81
01*
Basic/Adv
H01.05
Terminal S5 Select
Setting for S5.
--
00–81
0F*
Basic/Adv
H01.06
Terminal S6 Select
Setting for S6.
--
00–81
0F*
Basic/Adv
H01.07
Terminal S7 Select
Setting for S7.
--
00–81
0F*
Basic/Adv
00 Multi-Step Ref 2
Multi-Step Speed 2.
5-3
Basic/Adv
01 Multi-Step Ref 3
Multi-Step Speed 3.
5-3
Basic/Adv
02 Multi-Step Ref 4
Multi-Step Speed 4.
5-3
Basic/Adv
03 Multi-Step Ref 5
Multi-Step Speed 5.
5-3
Basic/Adv
04 Speed Hold 2
Hold function (2nd step of
Three-Step Infinitely Variable).
--
Basic/Adv
05 Accel Command
Acceleration function (2nd step
of Two-Step Infinitely Variable
or 3rd step of Three-Step
Infinitely Variable).
5-3
Basic/Adv
06 Upper Limit 1 N.O.
Upper Limit - SLOW DOWN;
Normally Open. UL1 - blinking
5-20
Basic/Adv
07 Upper Limit 2 N.O.
Upper Limit - STOP; Normally
Open. UL2 - blinking
5-20
Basic/Adv
08 Lower Limit 1 N.O.
Lower Limit - SLOW DOWN;
Normally Open. LL1 - blinking
5-20
Basic/Adv
* = Parameter defaults changed by X-Press Programming
Summary of Contents for 2001-G+M
Page 2: ......
Page 9: ...C h a p t e r 1 Introduction...
Page 10: ...IMPULSE G Mini Advanced Instruction Manual March 2014 1 2 This page intentionally left blank...
Page 16: ...IMPULSE G Mini Advanced Instruction Manual March 2014 1 8 This page intentionally left blank...
Page 17: ...C h a p t e r 2 Installation...
Page 18: ...IMPULSE G Mini Advanced Instruction Manual March 2014 2 2 This page intentionally left blank...
Page 25: ...C h a p t e r 3 Wiring...
Page 26: ...IMPULSE G Mini Advanced Instruction Manual March 2014 3 2 This page intentionally left blank...
Page 38: ...IMPULSE G Mini Advanced Instruction Manual March 2014 3 14 This page intentionally left blank...
Page 39: ...C h a p t e r 4 Getting Started...
Page 40: ...IMPULSE G Mini Advanced Instruction Manual March 2014 4 2 This page intentionally left blank...
Page 60: ...IMPULSE G Mini Advanced Instruction Manual March 2014 4 22 This page intentionally left blank...
Page 61: ...C h a p t e r 5 Programming Features...
Page 62: ...IMPULSE G Mini Advanced Instruction Manual March 2014 5 2 This page intentionally left blank...
Page 153: ...Troubleshooting IMPULSE G Mini C h a p t e r 6...
Page 154: ...IMPULSE G Mini Advanced Instruction Manual March 2014 6 2 This page intentionally left blank...
Page 165: ...IMPULSE G Mini Advanced Parameter Listing A p p e n d i x A...
Page 166: ...IMPULSE G Mini Advanced Instruction Manual March 2014 A 2 This page intentionally left blank...
Page 190: ...IMPULSE G Mini Advanced Instruction Manual March 2014 A 26 This page intentionally left blank...