IMPULSE•G+ Mini Advanced Instruction Manual - March 2014
3-6
Terminal Description
Type
Terminal
Name
Function (Signal Level)
Ma
in Cir
cu
it
R/L1,
S/L2,
T/L3
AC power supply input
AC power supply input
U/T1,
V/T2,
W/T3
Inverter output
Inverter output
B1, B2
Braking resistor connection
Braking resistor connection
+2, +1
DC reactor connection
When connecting optional DC reactor, remove the main circuit short-circuit bar b2
and +1.
+1, (–)
DC power supply input
DC power supply input (+1: positive; (–): negative)
Grounding
Ground to local grounding codes
Co
ntrol Circu
it
Inpu
t
Sequen
c
e
S1
Multi-function input selection 1
FWD run when closed, stop when open H01.01 ~
H01.07
120VAC ±10%
S2
Multi-function input selection 2
REV run when closed, stop when open
S3
Multi-function input selection 3
Inputs are programmable
S4
Multi-function input selection 4
S5
Multi-function input selection 5
S6
Multi-function input selection 6
S7
Multi-function input selection 7
X2*
Multi-function input selection
common
Common for control signal
Analo
g
In
put Sign
al
+V
+10.5V DC
Power supply output
For analog c10V power supply
+10V (Allowable current 20 mA max)
A1
Master frequency reference
0 to +10V/0 to 100%
0 to +10V/(2K Ohm)
A2
Multi-function analog reference
4 to 20 mA/0 to 100%
0 to 10V/0 to 100%
0 to 20 mA/0 to 100%
H03.09
4 to 20 mA (250 Ohm), 0 to +10V/(2k
Ohm)
AC
Frequency reference common
0V
0 to ±10V. Max ±5%
2mA or less
Saf
e
Disable In
put
HC
Power Supply for safe disable
input
+24 VDC (max 10 mA allowed)
H1
Safe disable input
Open: Output disabled
Closed: Normal Operation
NOTE:
Disconnect wire jumper between HC and H1 when using the safe disable input. See
Safe Disable Function on page 3-7.
RP
Pulse Input
Pulse Input frequency reference
H06.01
0 to 32kHz (3k
impedance) ±5%
High level voltages 3.5 to 13.2
Low level voltages 0.0 to 0.8
Duty Cycle (on/off) 30% to 70%
Out
p
ut
M
u
lt
i-function
contact
output
MP
Pulse Monitor
Pulse output frequency
H06.06
0 to 32kHz ±5% output (load: 1.5k
)
MA
NO contact output
Factory setting: brake output
H02.01
Dry contact capability:
250VAC 1A or less,
30VDC 1A or less
MB
NC contact output
MC
Contact output common
P1
Photo coupler output 1
Outputs are programmable
H02.02 ~
H02.03
Photo-coupler 48VDC, 50mA
or less
P2
Photo coupler output 2
PC
Photo coupler output common
0V
AM
Analog monitor output
Factory setting: output frequency 0 to
+10V
H04.01
+10VDC, 2mA or less, 8-bit resolution
AC
Analog monitor common
0V
C
o
mm
unication
C
ircuit T
ermi
n
al
ME
MOBUS
communicati
o
ns R+
Communications input (+)
MEMOBUS communication
Run through RS-485 or
RS-422.
H05.01 ~
H05.08
RS-485/422
MEMOBUS protocol, 115.2 kbps max.
R-
Communications input (-)
S+
Communications output (+)
S-
Communications output (-)
I(G)
Signal Common
Connection to shield sheath of signal lead
0V
* Terminal X2 is only available on the AC option cards. Terminal SC is used with the DC terminal board.
Summary of Contents for 2001-G+M
Page 2: ......
Page 9: ...C h a p t e r 1 Introduction...
Page 10: ...IMPULSE G Mini Advanced Instruction Manual March 2014 1 2 This page intentionally left blank...
Page 16: ...IMPULSE G Mini Advanced Instruction Manual March 2014 1 8 This page intentionally left blank...
Page 17: ...C h a p t e r 2 Installation...
Page 18: ...IMPULSE G Mini Advanced Instruction Manual March 2014 2 2 This page intentionally left blank...
Page 25: ...C h a p t e r 3 Wiring...
Page 26: ...IMPULSE G Mini Advanced Instruction Manual March 2014 3 2 This page intentionally left blank...
Page 38: ...IMPULSE G Mini Advanced Instruction Manual March 2014 3 14 This page intentionally left blank...
Page 39: ...C h a p t e r 4 Getting Started...
Page 40: ...IMPULSE G Mini Advanced Instruction Manual March 2014 4 2 This page intentionally left blank...
Page 60: ...IMPULSE G Mini Advanced Instruction Manual March 2014 4 22 This page intentionally left blank...
Page 61: ...C h a p t e r 5 Programming Features...
Page 62: ...IMPULSE G Mini Advanced Instruction Manual March 2014 5 2 This page intentionally left blank...
Page 153: ...Troubleshooting IMPULSE G Mini C h a p t e r 6...
Page 154: ...IMPULSE G Mini Advanced Instruction Manual March 2014 6 2 This page intentionally left blank...
Page 165: ...IMPULSE G Mini Advanced Parameter Listing A p p e n d i x A...
Page 166: ...IMPULSE G Mini Advanced Instruction Manual March 2014 A 2 This page intentionally left blank...
Page 190: ...IMPULSE G Mini Advanced Instruction Manual March 2014 A 26 This page intentionally left blank...