IMPULSE•G+ Mini Advanced Instruction Manual – March 2014
4-18
Initialize Parameters (A01.05)
Use this parameter to reset the drive to user-specified initial values or clear an oPE04 fault.
User Initialize (A01.05 = 1110)
Once the drive is configured and the system is running, set parameter O02.03 = 01 to save all
modified parameters to the User Initialized memory on the terminal board. Changing A01.05 = 1110
will recall all modified parameters back to the last time saved using O02.03.
oPE04 Fault (A01.05 = 5550)
The oPE04 fault indicates the parameters in the terminal board do not match the parameters of the
control board. To reset the oPE04 fault, set A01.05 = 5550. This will copy the parameters from the
terminal board to the control board. Check and verify your kVA setting (O02.04) before operating
the drive. Please contact Magnetek support for assistance.
Password Entry 1 (A01.06)
This parameter enables the user to set a password that inhibits the programming of parameters
A01.01 ~ A01.08 and locks the remaining parameters in the drive except those stored in the User
Parameter group, A02.xx.
To program a password, access the programming menu, “PAr”, and navigate to parameter A01.06.
Press the STOP and UP arrow keys at the same time to change the display from A01.06 to A01.07.
Press ENTER and program a password number into A01.07.
When parameters A01.06
A01.07, only parameters A01.01, A01.06, and A01.08 are visible and
cannot be modified. The Access Level is set to User Program (A01.01 = 0000). Parameters
programmed in A02.xx can be viewed in the “USEr” menu with read/write accessibility. When
A01.06 = A01.07, then A01.01 to A01.08 can be modified, along with the remaining parameters in
the drive.
When A01.06
A01.07, then A01.06 will show “LoC”. When A01.06 = A01.07, then A01.06 will
show “UnLoC”.
User Parameters (A02.01 through A02.32)
This function allows users to select up to 32 parameters for quick-access programming in the
“USEr” menu when the access level is set to User Program (A01.01 = 0000). This function is useful
when used in conjunction with A01.06, which locks all parameters in the drive except those stored in
the User Parameter Group, A02.xx.
To assign a parameter as a user parameter, change the Access Level to Advanced (A01.01 = 0002),
go to the A02 function group and select an A02.01 ~ A02.32 parameter. Press ENTER. The display
will show “----”. Use the UP or DOWN arrow keys to select a user parameter and press ENTER
when done.
Setting
Description
0000
No Initialize (factory default)
1110
User Initialize - Restores the drive to user-specified initial values.
5550
Copies save parameters back from terminal to the drive’s memory
Summary of Contents for 2001-G+M
Page 2: ......
Page 9: ...C h a p t e r 1 Introduction...
Page 10: ...IMPULSE G Mini Advanced Instruction Manual March 2014 1 2 This page intentionally left blank...
Page 16: ...IMPULSE G Mini Advanced Instruction Manual March 2014 1 8 This page intentionally left blank...
Page 17: ...C h a p t e r 2 Installation...
Page 18: ...IMPULSE G Mini Advanced Instruction Manual March 2014 2 2 This page intentionally left blank...
Page 25: ...C h a p t e r 3 Wiring...
Page 26: ...IMPULSE G Mini Advanced Instruction Manual March 2014 3 2 This page intentionally left blank...
Page 38: ...IMPULSE G Mini Advanced Instruction Manual March 2014 3 14 This page intentionally left blank...
Page 39: ...C h a p t e r 4 Getting Started...
Page 40: ...IMPULSE G Mini Advanced Instruction Manual March 2014 4 2 This page intentionally left blank...
Page 60: ...IMPULSE G Mini Advanced Instruction Manual March 2014 4 22 This page intentionally left blank...
Page 61: ...C h a p t e r 5 Programming Features...
Page 62: ...IMPULSE G Mini Advanced Instruction Manual March 2014 5 2 This page intentionally left blank...
Page 153: ...Troubleshooting IMPULSE G Mini C h a p t e r 6...
Page 154: ...IMPULSE G Mini Advanced Instruction Manual March 2014 6 2 This page intentionally left blank...
Page 165: ...IMPULSE G Mini Advanced Parameter Listing A p p e n d i x A...
Page 166: ...IMPULSE G Mini Advanced Instruction Manual March 2014 A 2 This page intentionally left blank...
Page 190: ...IMPULSE G Mini Advanced Instruction Manual March 2014 A 26 This page intentionally left blank...