![Lust MASTERCONTROL MC6000 Series Instruction Manual Download Page 23](http://html1.mh-extra.com/html/lust/mastercontrol-mc6000-series/mastercontrol-mc6000-series_instruction-manual_1950408023.webp)
Instruction Manual MC6000
2-3
Code Unit MC6404 MC6408 MC6412 MC6416 MC6432 MC6464
Protection
IP20, VBG4
Mounting orientation
vertical, wall mounted
Weight
m
kg
6
7,5
10
15
Dimensions
A
mm
5,8
7
B
mm
360
440
C
mm
345
425
D
mm
95
142,5
190
285
E
mm
7,5
F
mm
60
100
150
240
G
mm
260
290
2.6
Dimensions and weights
B
C
D
G
s t o p
r e t u r n
s t a r t
e n t e r
S M A R T
C A R D
A
F
E
CTRL
min-1
Code Unit MC6404 MC6408 MC6412 MC6416 MC6432 MC6464
Cooling air temperature
T
°C
0 - 40
(up to 1000 m a.s.l.)
Type of cooling
forced cooling
Relative humidity
rF
%
15 - 85, non condensing (VDE0160)
Power reduction relative
P
%
5 %/°C above 40°C cooling air temperature
to cooling air temperature
max. 50°C
Power reduction relative
P
%
5 % per 1000 m above 1000 m a.s.l.,
to installation height
max. 2000 m a.s.l.
Storage temperature
T
°C
-25 - +55 (VDE0160)
Transport temparature
T
°C
-25 - +70 (VDE0160)
Vibration (IEC 68-2-6)
2g (IEC68-2-6)
5) When equipped with I/O Module 1 (version AH1) maximum cooling air temperature 40 degrees C
2.5
Ambient conditions