Instruction Manual MC6000
10-32
SERR
Serial Error State
Serial interface error status
Parameter number:
85
Physical unit:
hexadecimal
Value range:
see table below
Factory setting:
00h
Customer setting:
Display level:
3
Editing level:
cannot be edited
S
MART
C
ARD
area:
no data storage
SWDGT
Serial Watchdog Time
Serial interface watchdog cycle time.
This is the time within which the Bus master must have
sent at least 1 telegram to the Servocontroller. If the
Servocontroller does not receive the telegram, error E-
WDG (Watchdog) with error location 11 will be displayed.
Parameter number:
84
Physical unit:
s
Value range:
0.00 - 20.00
Factory setting:
0.00
Customer setting:
Display level:
3
Editing level:
3
S
MART
C
ARD
area:
SYSTM
Note:
The setting SWDGT= 0.00 switches the Watchdog off.
Bit positionHex
Title
Meaning
0
01 H
Power on
Bit is set each time power is switched on
1
02 H
Watchdog
Watchdog has detected timeout
2
04 H
EEPROM busy
The EEPROM is currently busy
saving
3
08 H
Checksum error
Data transfer error
Checksum invalid
5
20 H
No parameter
There is no parameter in the device
with the parameter number transmitted
6
40 H
No change
Changes to parameters not permitted
7
80 H
Invalid value
The parameter value transmitted is invalid
_CONF
_ENCD
_OPT2
_OPT1
_MOT
_TCON
_SCON
_PCON
_SIO
_KPAD
_SCTY
_REF