Instruction Manual MC6000
10-43
RA0, RA1
Reference from Analog Input 0, 1
Analog input 0 (ISA0) and 1 (ISA1),
1
)
Parameter only for display of digitized value
Parameter number:
425, 426
Physical unit:
Nm, Umin
-1
or r (depending on control mode)
Value range:
-32764 - 32764
Factory setting:
0
Customer setting:
Display level:
2
Editing level:
cannot be edited
S
MART
C
ARD
area:
ALL
RDIG
Reference from Digital Input
Digital reference input
Parameter number:
430
Physical unit:
Nm, min
-1
or r (depending on control mode)
Value range:
-32764 - 32764
Factory setting:
0
Customer setting:
Display level:
2
Editing level:
cannot be edited
S
MART
C
ARD
area:
ALL
REF1, REF2, REF3, REF4, REF5, REF6
Reference Value 1 - 6
Intermediate values of the reference value input,
parameters to display the reference value on the
reference channels
Parameter number:
433, 434, 435, 436, 437, 438
Physical unit:
Nm, min
-1
or r (depending on control mode)
Value range:
-32764 - 32764
Factory setting:
0
Customer setting:
Display level:
3
Editing level:
cannot be edited
S
MART
C
ARD
area:
ALL
RF3FA
Reference Channel 3 Factor
Factor for scaling the reference value on channel 3
Parameter number:
448
Physical unit:
%
Value range:
0 - 100
Factory setting:
100
Customer setting:
Display level:
2
Editing level:
2
S
MART
C
ARD
area:
REFRC
Changes effective:
only after re-initializing (see Section 6.7)
_CONF
_ENCD
_OPT2
_OPT1
_MOT
_TCON
_SCON
_PCON
_SIO
_KPAD
_SCTY
_REF