![Lust MASTERCONTROL MC6000 Series Instruction Manual Download Page 103](http://html1.mh-extra.com/html/lust/mastercontrol-mc6000-series/mastercontrol-mc6000-series_instruction-manual_1950408103.webp)
Instruction Manual MC6000
9-5
9.2.4
Troubleshooting
Possible causes of a function not working as as expected:
Symptom
Solution
Reference value present, but drive does not turn
- ENPO = High level
- select correct control location CLSEL
(_CONF)
- use START command
- check function selectors for analog
inputs
Drive turns but reference value cannot be
- use reference value 3 or 4
inverted (eg change of direction of rotation
RSSL3, RSSL4 (_REF)
not possible)
Drive does not turn with required reference value
- switch off reference value channels
not in use RSSLx= RCON (_REF)
- switch off Offset for selectors
FIxxx not = ADx-y (_CONF)
Ramps inactive
- set parameters for ramps ACCR
and DECR (_REF)
- use reference value channel 3 or 4
RSSL3, RSSL4 (_REF)