Instruction Manual MC6000
10-6
Parameter setting range:
The setting range for parameters is only a theorectical range which cannot be used by every
drive. For example ramp parameters ACCR and DECR can be set =65536 min
-1
s
-1
. In practice
however, depending on moments of inertia and the torque available, the maximum acceleration
or deceleration is likely to be in the range 20,000 to 30,000 min
-1
s
-1
. If higher parameter levels
are set the drive will run at maximum torque until reaching the reference speed.
Setting parameters using serial interface (RS485, InterBus-S, CAN-Bus):
Possible parameter settings are listed under "Value range" in { } and in tables under "No." .
Allocation of user levels and S
MART
C
ARD
areas:
Note:
Parameters which depend on the hardware present or which are derived from software settings
are not stored on the S
MART
C
ARD
. These parameters are identified with "no data storage", eg
Hardware- and Software Status word (CFHSW and CFSSW in area _CONF).