Installing the Inverter
47
Step 5 PNP/NPN Mode Selection
The S100 inverter supports both PNP (Source) and NPN (Sink) modes for sequence inputs
at the terminal. Select an appropriate mode to suit requirements using the PNP/NPN
selection switch (SW1) on the control board. Refer to the following information for detailed
applications.
PNP Mode (Source)
Select PNP using the PNP/NPN selection switch (SW1). Note that the factory default
setting is NPN mode. CM is the common ground terminal for all analog inputs at the
terminal, and P24 is 24V internal source. If you are using an external 24V source, build a
circuit that connects the external source (-) and the CM terminal.
Summary of Contents for LSLV-S100 Series
Page 1: ......
Page 11: ...Preparing the Installation 2 ...
Page 13: ...Preparing the Installation 4 5 5 22kW 3 Phase ...
Page 16: ...Preparing the Installation 7 Front cover removed ...
Page 45: ...Installing the Inverter 36 IP66 0 4 0 8kW 3 phase 1 5 2 2kW 3 phase ...
Page 50: ...Installing the Inverter 41 0 4 22kW Standard I O Multiple I O ...
Page 67: ...Installing the Inverter 58 ...
Page 69: ...Learning to Perform Basic Operations 60 30 75kW Models ...
Page 193: ...Table of Functions 184 ...
Page 205: ...196 Troubleshooting ...
Page 228: ...Technical Specification 219 30 75kW Models 30 kW 3 Phase 37 45 kW 3 Phase ...
Page 230: ...Technical Specification 221 IP66 Models 0 4 4 0kW NP Non PDS type ...
Page 231: ...Technical Specification 222 0 4 4 0kW PDS type ...
Page 233: ...Technical Specification 224 5 5 7 5kW NP Non PDS type ...
Page 235: ...Technical Specification 226 11 0 22 0kW NP Non PDS type ...
Page 259: ...250 ...
Page 261: ...252 ...
Page 263: ...254 ...