141
4.8
Communication Function group (PAR
→
CM)
In the following table, the data shaded in grey will be displayed when a related code has
been selected.
SL
: Sensorless vector control (dr.09) , I – IM Sensorless, P – PM Sensorless
*
O/X:
Write-enabled during operation,
7/L/A
: Keypad/LCD keypad/Common
Code
Comm.
Address
Name
LCD
Display
Setting Range
Initial
Value
Property* V/F SL
00
-
Jump Code
Jump
Code
1-99
20
O/A
O I/P
01 0h1701
Built-in
communication
inverter ID
Int485 St
ID
1-250
1
O/A
O I/P
02
53
0h1702
Built-in
communication
protocol
Int485
Proto
0
ModBus
RTU
0:
ModBus
RTU
O/A
O I/P
2 LS Inv 485
Built-in
communication
speed
Int485
BaudR
0 1200 bps
3:
9600
bps
O/A
O I/P
1 2400 bps
2 4800 bps
3 9600 bps
4 19200 bps
5 38400 bps
6 56 Kbps
7 115 Kbps
54
Built-in
communication
frame setting
Int485
Mode
0 D8/PN/S1
0:
D8/PN/S1
O/A
O I/P
1 D8/PN/S2
2 D8/PE/S1
3 D8/PO/S1
Transmission
delay
after reception
Resp
Delay
0-1000(ms)
5ms
O/A
O I/P
06
55
0h1706
Communication
option
S/W version
FBus S/W
Ver
-
0.00
O/A
O I/P
Communication
option
inverter ID
FBus ID
0-255
1
O/A
O I/P
53
Will not be displayed when P2P and MultiKPD is set.
54
115,200bps
55
Displayed only when a communication option card is installed.
Summary of Contents for LSLV-S100 Series
Page 1: ......
Page 11: ...Preparing the Installation 2 ...
Page 13: ...Preparing the Installation 4 5 5 22kW 3 Phase ...
Page 16: ...Preparing the Installation 7 Front cover removed ...
Page 45: ...Installing the Inverter 36 IP66 0 4 0 8kW 3 phase 1 5 2 2kW 3 phase ...
Page 50: ...Installing the Inverter 41 0 4 22kW Standard I O Multiple I O ...
Page 67: ...Installing the Inverter 58 ...
Page 69: ...Learning to Perform Basic Operations 60 30 75kW Models ...
Page 193: ...Table of Functions 184 ...
Page 205: ...196 Troubleshooting ...
Page 228: ...Technical Specification 219 30 75kW Models 30 kW 3 Phase 37 45 kW 3 Phase ...
Page 230: ...Technical Specification 221 IP66 Models 0 4 4 0kW NP Non PDS type ...
Page 231: ...Technical Specification 222 0 4 4 0kW PDS type ...
Page 233: ...Technical Specification 224 5 5 7 5kW NP Non PDS type ...
Page 235: ...Technical Specification 226 11 0 22 0kW NP Non PDS type ...
Page 259: ...250 ...
Page 261: ...252 ...
Page 263: ...254 ...