Troubleshooting
193
Type
Cause
Remedy
model with increased capacity.
The motor
rotates in the
opposite
direction to the
command.
The wiring for the motor output cable is
incorrect.
Determine if the cable on the output
side is wired correctly to the phase
(U/V/W) of the motor.
The signal connection between the
control circuit terminal (forward/reverse
rotation) of the inverter and the
forward/reverse rotation signal on the
control panel side is incorrect.
Check the forward/reverse rotation
wiring.
The motor only
rotates in one
direction.
Reverse rotation prevention is
selected.
Remove the reverse rotation
prevention.
The reverse rotation signal is not
provided, even when a 3-wire
sequence is selected.
Check the input signal associated
with the 3-wire operation and adjust
as necessary.
The motor is
overheating.
The load is too heavy.
Reduce the load.
Increase the Acc/Dec time.
Check the motor parameters and
set the correct values.
Replace the motor and the inverter
with models with appropriate
capacity for the load.
The ambient temperature of the motor
is too high.
Lower the ambient temperature of
the motor.
The phase-to-phase voltage of the
motor is insufficient.
Use a motor that can withstand
phase-to-phase voltages surges
greater than the maximum surge
voltage.
Only use motors suitable for
applications with inverters.
Connect the AC reactor to the
inverter output (set the carrier
frequency to 2 kHz).
The motor fan has stopped or the fan is
obstructed with debris.
Check the motor fan and remove
any foreign objects.
The motor stops
during
acceleration or
when
connected to
load.
The load is too high.
Reduce the load.
Replace the motor and the inverter
with models with capacity
appropriate for the load.
The motor does
not accelerate.
/The
acceleration
time is too long.
The frequency command value is low. Set an appropriate value.
The load is too high.
Reduce the load and increase the
acceleration time. Check the
mechanical brake status.
The acceleration time is too long.
Change the acceleration time.
Summary of Contents for LSLV-S100 Series
Page 1: ......
Page 11: ...Preparing the Installation 2 ...
Page 13: ...Preparing the Installation 4 5 5 22kW 3 Phase ...
Page 16: ...Preparing the Installation 7 Front cover removed ...
Page 45: ...Installing the Inverter 36 IP66 0 4 0 8kW 3 phase 1 5 2 2kW 3 phase ...
Page 50: ...Installing the Inverter 41 0 4 22kW Standard I O Multiple I O ...
Page 67: ...Installing the Inverter 58 ...
Page 69: ...Learning to Perform Basic Operations 60 30 75kW Models ...
Page 193: ...Table of Functions 184 ...
Page 205: ...196 Troubleshooting ...
Page 228: ...Technical Specification 219 30 75kW Models 30 kW 3 Phase 37 45 kW 3 Phase ...
Page 230: ...Technical Specification 221 IP66 Models 0 4 4 0kW NP Non PDS type ...
Page 231: ...Technical Specification 222 0 4 4 0kW PDS type ...
Page 233: ...Technical Specification 224 5 5 7 5kW NP Non PDS type ...
Page 235: ...Technical Specification 226 11 0 22 0kW NP Non PDS type ...
Page 259: ...250 ...
Page 261: ...252 ...
Page 263: ...254 ...