Technical Specification
242
Continuous Rated Current Derating by Input Voltage
The continuous rated current of the inverter is limited based on the input voltage. Refer to
the following graph.
Continuous Rated Current Derating by Ambient Temperature and Installation Type
The constant-rated current of the inverter is limited based on the ambient temperature and
installation type. Refer to the following graph. A side-by-side operation is only available with
0.4-22kW IP20.
C
on
tin
uo
us
ra
te
d
cu
rr
en
t
Input Voltage