Table of Functions
115
4.4
Expanded Function group (PAR
→
Ad)
In the following table, the data shaded in grey will be displayed when a related code has
been selected.
SL
: Sensorless vector control (dr.09) , I – IM Sensorless, P – PM Sensorless
*
O/X
: Write-enabled during operation,
7/L/A
: Keypad/LCD keypad/Common
Code
Comm.
Address
Name
LCD Display
Setting Range
Initial
Value
Property* V/F SL
00
-
Jump Code
Jump Code 1-99
24
O/A
O I/P
01
0h1301 Acceleration
pattern
Acc Pattern 0 Linear
0: Linear
X/A
O I/P
02
0h1302
Deceleration
pattern
Dec Pattern 1 S-curve
X/A
O I/P
03
14
0h1303
S-curve
acceleration
start point
gradient
Acc S Start 1-100(%)
40
X/A
O I/P
S-curve
acceleration
end point
gradient
Acc S End
1-100(%)
40
X/A
O I/P
05
15
0h1305
S-curve
deceleration
start point
gradient
Dec S Start 1-100(%)
40
X/A
O I/P
S-curve
deceleration
end point
gradient
Dec S End
1-100(%)
40
X/A
O I/P
07
0h1307 Start Mode
Start Mode
0 Acc
0:Acc
X/A
O I/P
1 DC-Start
08
16
0h1308 Stop Mode
Stop Mode
0 Dec
0:Dec
X/A
O I/P
1 DC-Brake
2 Free-Run
4
Power
Braking
09
0h1309
Selection of
prohibited
rotation
Run Prevent
0 None
0: None X/A
O I/P
1
Forward
Prev
14
Displayed when Ad. 01 is set to 1 (S-curve).
15
Displayed when Ad. 02 is set to 1 (S-curve).
16
DC braking and power braking (Ad.08, stop mode options 1 and 4) are not available
when dr.09 (Control Mode) is set to 6 (PM Sensorless).
Summary of Contents for LSLV-S100 Series
Page 1: ......
Page 11: ...Preparing the Installation 2 ...
Page 13: ...Preparing the Installation 4 5 5 22kW 3 Phase ...
Page 16: ...Preparing the Installation 7 Front cover removed ...
Page 45: ...Installing the Inverter 36 IP66 0 4 0 8kW 3 phase 1 5 2 2kW 3 phase ...
Page 50: ...Installing the Inverter 41 0 4 22kW Standard I O Multiple I O ...
Page 67: ...Installing the Inverter 58 ...
Page 69: ...Learning to Perform Basic Operations 60 30 75kW Models ...
Page 193: ...Table of Functions 184 ...
Page 205: ...196 Troubleshooting ...
Page 228: ...Technical Specification 219 30 75kW Models 30 kW 3 Phase 37 45 kW 3 Phase ...
Page 230: ...Technical Specification 221 IP66 Models 0 4 4 0kW NP Non PDS type ...
Page 231: ...Technical Specification 222 0 4 4 0kW PDS type ...
Page 233: ...Technical Specification 224 5 5 7 5kW NP Non PDS type ...
Page 235: ...Technical Specification 226 11 0 22 0kW NP Non PDS type ...
Page 259: ...250 ...
Page 261: ...252 ...
Page 263: ...254 ...