
Troubleshooting
195
Type
Cause
Remedy
Check the capacity of the earth
leakage breaker and make the
appropriate connection, based on
the rated current of the inverter.
Lower the carrier frequency.
Make the cable length between the
inverter and the motor as short as
possible.
The motor
vibrates
severely and
does not rotate
normally.
Phase-to-phase voltage of 3-phase
power source is not balanced.
Check the input voltage and balance
the voltage.
Check and test the motor’s
insulation.
The motor
makes
humming, or
loud noises.
Resonance occurs between the
motor's natural frequency and the
carrier frequency.
Slightly increase or decrease the
carrier frequency.
Resonance occurs between the
motor's natural frequency and the
inverter’s output frequency.
Slightly increase or decrease the
carrier frequency.
Use the frequency jump function to
avoid the frequency band where
resonance occurs.
The motor
vibrates/hunts.
The frequency input command is an
external, analog command.
In situations of noise inflow on the
analog input side that results in
command interference, change the
input filter time constant (In.07).
The wiring length between the inverter
and the motor is too long.
Ensure that the total cable length
between the inverter and the motor
is less than 200m (50m for motors
rated 3.7 kW or lower).
The motor does
not come to a
complete stop
when the
inverter output
stops.
It is difficult to decelerate sufficiently,
because DC braking is not operating
normally.
Adjust the DC braking parameter.
Increase the set value for the DC
braking current.
Increase the set value for the DC
braking stopping time.
The output
frequency does
not increase to
the frequency
reference.
The frequency reference is within the
jump frequency range.
Set the frequency reference higher
than the jump frequency range.
The frequency reference is exceeding
the upper limit of the frequency
command.
Set the upper limit of the frequency
command higher than the frequency
reference.
Because the load is too heavy, the stall
prevention function is working.
Replace the inverter with a model
with increased capacity.
The cooling fan
does not rotate.
The control parameter for the cooling
fan is set incorrectly.
Check the control parameter setting
for the cooling fan.
Summary of Contents for LSLV-S100 Series
Page 1: ......
Page 11: ...Preparing the Installation 2 ...
Page 13: ...Preparing the Installation 4 5 5 22kW 3 Phase ...
Page 16: ...Preparing the Installation 7 Front cover removed ...
Page 45: ...Installing the Inverter 36 IP66 0 4 0 8kW 3 phase 1 5 2 2kW 3 phase ...
Page 50: ...Installing the Inverter 41 0 4 22kW Standard I O Multiple I O ...
Page 67: ...Installing the Inverter 58 ...
Page 69: ...Learning to Perform Basic Operations 60 30 75kW Models ...
Page 193: ...Table of Functions 184 ...
Page 205: ...196 Troubleshooting ...
Page 228: ...Technical Specification 219 30 75kW Models 30 kW 3 Phase 37 45 kW 3 Phase ...
Page 230: ...Technical Specification 221 IP66 Models 0 4 4 0kW NP Non PDS type ...
Page 231: ...Technical Specification 222 0 4 4 0kW PDS type ...
Page 233: ...Technical Specification 224 5 5 7 5kW NP Non PDS type ...
Page 235: ...Technical Specification 226 11 0 22 0kW NP Non PDS type ...
Page 259: ...250 ...
Page 261: ...252 ...
Page 263: ...254 ...