Troubleshooting
187
Protection Functions Using Abnormal Internal Circuit Conditions and External
Signals
Keypad
Display
LCD Display
Type
Description
Over Heat
Latch
Displayed when the temperature of the inverter heat
sink exceeds the specified value.
Over
Current2
Latch
Displayed when the DC circuit in the inverter detects a
specified level of excessive, short circuit current.
External Trip Latch
Displayed when an external fault signal is provided by
the multi-function terminal. Set one of the multi-function
input terminals at In.65-71 to 4 (External Trip) to enable
external trip.
BX
Level
Displayed when the inverter output is blocked by a
signal provided from the multi-function terminal. Set
one of the multi-function input terminals at In.65-71 to 5
(BX) to enable input block function.
H/W-Diag
Fatal
Displayed when an error is detected in the memory
(EEPRom), analog-digital converter output (ADC Off
Set), or CPU watchdog (Watch Dog-1, Watch Dog-2).
EEP Err: An error in reading/writing parameters due to
keypad or memory (EEPRom) fault.
ADC Off Set: An error in the current sensing circuit
(U/V/W terminal, current sensor, etc.).
NTC Open
Latch
Displayed when an error is detected in the temperature
sensor of the Insulated Gate Bipolar Transistor (IGBT).
Fan Trip
Latch
Displayed when an error is detected in the cooling fan.
Set Pr.79 to 0 to activate fan trip (for models below
22kW capacity).
Pre-PID Fail Latch
Displayed when pre-PID is operating with functions set
at AP.34–AP.36. A fault trip occurs when a controlled
variable (PID feedback) is measured below the set
value and the low feedback continues, as it is treated
as a load fault.
Ext-Brake
Latch
Operates when the external brake signal is provided by
the multi-function terminal. Occurs when the inverter
output starting current remains below the set value at
Ad.41. Set either OU.31 or OU.32 to 35 (BR Control).
Safety A(B)
Err
Latch
Displayed when at least one of the two safety input
signals is off.
oht
oc2
ext
bx
hwt
ntc
fan
pid
xbr
sfb
sfa
Summary of Contents for LSLV-S100 Series
Page 1: ......
Page 11: ...Preparing the Installation 2 ...
Page 13: ...Preparing the Installation 4 5 5 22kW 3 Phase ...
Page 16: ...Preparing the Installation 7 Front cover removed ...
Page 45: ...Installing the Inverter 36 IP66 0 4 0 8kW 3 phase 1 5 2 2kW 3 phase ...
Page 50: ...Installing the Inverter 41 0 4 22kW Standard I O Multiple I O ...
Page 67: ...Installing the Inverter 58 ...
Page 69: ...Learning to Perform Basic Operations 60 30 75kW Models ...
Page 193: ...Table of Functions 184 ...
Page 205: ...196 Troubleshooting ...
Page 228: ...Technical Specification 219 30 75kW Models 30 kW 3 Phase 37 45 kW 3 Phase ...
Page 230: ...Technical Specification 221 IP66 Models 0 4 4 0kW NP Non PDS type ...
Page 231: ...Technical Specification 222 0 4 4 0kW PDS type ...
Page 233: ...Technical Specification 224 5 5 7 5kW NP Non PDS type ...
Page 235: ...Technical Specification 226 11 0 22 0kW NP Non PDS type ...
Page 259: ...250 ...
Page 261: ...252 ...
Page 263: ...254 ...