Table of Functions
103
4
Table of Functions
This chapter lists all the function settings for S100 series inverter. Set the parameters
required according to the following references. If a set value input is out of range, the
following messages will be displayed on the keyboard. In these cases, the inverter will not
operate with the [ENT] key.
•
Set value not allocated:
rd
•
Set value repetition (multi-function input, PID reference, PID feedback related):
OL
•
Set value not allowed (select value, V2, I2):
no
4.1
Operation Group
The Operation group is used only in the basic keypad mode. It will not be displayed on an
LCD loader.
SL
: Sensorless vector control (dr.09) , I – IM Sensorless, P – PM Sensorless
*
O/X
: Write-enabled during operation,
7/L/A
: Keypad/LCD keypad/Common
Code
Comm.
Address
Name
Keypad
Display
Setting Range
Initial
Value
Property* V/F SL
0h1F00
Target
frequency
0.00
0-Maximum
frequency(Hz)
0.00
O/7
O I/P
-
0h1F01
Acceleration
time
ACC
0.0-600.0(s)
20.0
O/7
O I/P
-
0h1F02
Deceleration
time
dEC
0.0-600.0(s)
30.0
O/7
O I/P
-
0h1F03
Command
source
drv
0
Keypad
1:
Fx/Rx-1
X/7
O I/P
1
Fx/Rx-1
2
Fx/Rx-2
3
Int 485
4
Field Bus
1
-
0h1F04
Frequency
reference
source
Frq
0
Keypad-1
0:
Keypad
-
1
X/7
O I/P
1
Keypad-2
2
V1
4
V2
5
I2
6
Int 485
8
Field Bus
12
Pulse
-
0h1F05 Multi-step
St1
0.00-Maximum
10.00
O/7
O I/P
1
Table of options are provided separately in the option manual.
Summary of Contents for LSLV-S100 Series
Page 1: ......
Page 11: ...Preparing the Installation 2 ...
Page 13: ...Preparing the Installation 4 5 5 22kW 3 Phase ...
Page 16: ...Preparing the Installation 7 Front cover removed ...
Page 45: ...Installing the Inverter 36 IP66 0 4 0 8kW 3 phase 1 5 2 2kW 3 phase ...
Page 50: ...Installing the Inverter 41 0 4 22kW Standard I O Multiple I O ...
Page 67: ...Installing the Inverter 58 ...
Page 69: ...Learning to Perform Basic Operations 60 30 75kW Models ...
Page 193: ...Table of Functions 184 ...
Page 205: ...196 Troubleshooting ...
Page 228: ...Technical Specification 219 30 75kW Models 30 kW 3 Phase 37 45 kW 3 Phase ...
Page 230: ...Technical Specification 221 IP66 Models 0 4 4 0kW NP Non PDS type ...
Page 231: ...Technical Specification 222 0 4 4 0kW PDS type ...
Page 233: ...Technical Specification 224 5 5 7 5kW NP Non PDS type ...
Page 235: ...Technical Specification 226 11 0 22 0kW NP Non PDS type ...
Page 259: ...250 ...
Page 261: ...252 ...
Page 263: ...254 ...