Technical Specification
205
3 Phase 200V (5.5-15 kW)
Model
□□□□
S100–2
□□□□□
0055
0075
0110
0150
Applied
motor
Heavy load
HP
7.5
10
15
20
kW
5.5
7.5
11
15
Normal load
HP
10
15
20
25
kW
7.5
11
15
18.5
Rated
output
Rated
capacity
(kVA)
Heavy
load
9.1
12.2
17.5
22.9
Normal
load
11.4
15.2
21.3
26.3
Rated
current [3-
Phase input]
(A)
Heavy
load
24.0
32.0
46.0
60.0
Normal
load
30.0
40.0
56.0
69.0
Rated
current
[Single-
Phase input]
(A)
Heavy
load
13.0
18.0
26.0
33.0
Normal
load
16.0
22.0
31.0
38.0
Output frequency
0-400 Hz (IM Sensorless : 0-120 Hz)
Output voltage (V)
3 phase 200-240V
Rated
input
Working voltage (V)
3 phase 200-240VAC (-15% to +10%)
Single phase 240VAC(-5% to +10%)
Input frequency
50-60 Hz (
5%)
(In case of single phase input, input frequency is only
60Hz(
5%)
.)
Rated
current (A)
Heavy
load
25.8
34.9
50.8
66.7
Normal
load
32.7
44.2
62.3
77.2
Weight
(lb/kg)
Non-EMC Filter Type
6.8/3.1
6.8/3.1
9.7/4.4
15.2/6.9
IP66 Type(Non-EMC)
19.4/8.8
19.4/8.8
20.7/9.4
26.2/11.9
•
The standard motor capacity is based on a standard 4-pole motor
•
The standard used for 200 V inverters is based on a 220 V supply voltage, and for
400V inverters is based on a 440 V supply voltage.
•
The rated output current is limited based on the carrier frequency set at Cn.04.
•
IP66 models do not support normal load operation.
Summary of Contents for LSLV-S100 Series
Page 1: ......
Page 11: ...Preparing the Installation 2 ...
Page 13: ...Preparing the Installation 4 5 5 22kW 3 Phase ...
Page 16: ...Preparing the Installation 7 Front cover removed ...
Page 45: ...Installing the Inverter 36 IP66 0 4 0 8kW 3 phase 1 5 2 2kW 3 phase ...
Page 50: ...Installing the Inverter 41 0 4 22kW Standard I O Multiple I O ...
Page 67: ...Installing the Inverter 58 ...
Page 69: ...Learning to Perform Basic Operations 60 30 75kW Models ...
Page 193: ...Table of Functions 184 ...
Page 205: ...196 Troubleshooting ...
Page 228: ...Technical Specification 219 30 75kW Models 30 kW 3 Phase 37 45 kW 3 Phase ...
Page 230: ...Technical Specification 221 IP66 Models 0 4 4 0kW NP Non PDS type ...
Page 231: ...Technical Specification 222 0 4 4 0kW PDS type ...
Page 233: ...Technical Specification 224 5 5 7 5kW NP Non PDS type ...
Page 235: ...Technical Specification 226 11 0 22 0kW NP Non PDS type ...
Page 259: ...250 ...
Page 261: ...252 ...
Page 263: ...254 ...