Table of Functions
137
Code
Comm.
Address
Name
LCD
Display
Setting Range
Initial
Value
Property* V/F SL
4 Torque
5 Output Power
6 Idse
7 Iqse
8 Target Freq
9 Ramp Freq
10 Speed Fdb
12 PID Ref Value
13 PID Fdb Value
14 PID Output
15 Constant
08 0h1608
Analog
output 2
gain
AO2 Gain -1000.0~1000.0(%) 100.0
O/A
O I/P
09 0h1609
Analog
output 2 bias
AO2 Bias -100.0~100.0(%) 0.0
O/A
O I/P
10 0h160A
Analog
output 2 filter
AO2 Filter 0~10000(ms)
5
O/A
O I/P
11 0h160B
Analog
constant
output 2
AO2
Const %
0.0~100.0(%)
0.0
O/A
O I/P
12 0h160C
Analog
output 2
monitor
AO2
Monitor
0.0~1000.0(%)
0.0
-
/A
O I/P
30 0h161E
Fault output
item
Trip Out
Mode
bit 000-111
010
51
O/A
O I/P
1 Low voltage
2
Any faults
other than low
voltage
3
Automatic
restart final
failure
31
(32)
0h161F
(0h1620
)
Multi-
function
relay 1 item
(Relay 2)
Relay 1
(Relay 2)
0 None
29:Trip
(14:Run)
O/A
O I/P
1 FDT-1
2 FDT-2
3 FDT-3
4 FDT-4
5 Over Load
6 IOL
7 Under Load
8 Fan Warning
51
The initial value 0010 will be displayed on the keypad as
.
Summary of Contents for LSLV-S100 Series
Page 1: ......
Page 11: ...Preparing the Installation 2 ...
Page 13: ...Preparing the Installation 4 5 5 22kW 3 Phase ...
Page 16: ...Preparing the Installation 7 Front cover removed ...
Page 45: ...Installing the Inverter 36 IP66 0 4 0 8kW 3 phase 1 5 2 2kW 3 phase ...
Page 50: ...Installing the Inverter 41 0 4 22kW Standard I O Multiple I O ...
Page 67: ...Installing the Inverter 58 ...
Page 69: ...Learning to Perform Basic Operations 60 30 75kW Models ...
Page 193: ...Table of Functions 184 ...
Page 205: ...196 Troubleshooting ...
Page 228: ...Technical Specification 219 30 75kW Models 30 kW 3 Phase 37 45 kW 3 Phase ...
Page 230: ...Technical Specification 221 IP66 Models 0 4 4 0kW NP Non PDS type ...
Page 231: ...Technical Specification 222 0 4 4 0kW PDS type ...
Page 233: ...Technical Specification 224 5 5 7 5kW NP Non PDS type ...
Page 235: ...Technical Specification 226 11 0 22 0kW NP Non PDS type ...
Page 259: ...250 ...
Page 261: ...252 ...
Page 263: ...254 ...