Preparing the Installation
14
Ground Cable and Power Cable Specifications (30-75kW)
Load (kW)
Ground
Power I/O
mm
2
AWG
mm
2
AWG
R/S/T
U/V/W
R/S/T
U/V/W
3–Phase
400V
30
16
5
25
25
4
4
37
45
70
70
1/0
1/0
55
35
3
75
2
Signal (Control) Cable Specifications
Terminals
Signal Cable
Without Crimp Terminal
Connectors
(Bare wire)
With Crimp Terminal Connectors
(Bootlace Ferrule)
mm
2
AWG
mm
2
AWG
P1~P7*/CM/VR/V1/I2
/AO1,AO2/Q1/EG/24/TI/
TO* /SA,SB,SC/S+,
S-,SG
0.75
18
0.5
20
A1/B1/C1/A2/C2
1.0
17
1.5
15
* Standard I/O doesn’t support P6/P7/TI/TO terminal. Refer to
on page
Summary of Contents for LSLV-S100 Series
Page 1: ......
Page 11: ...Preparing the Installation 2 ...
Page 13: ...Preparing the Installation 4 5 5 22kW 3 Phase ...
Page 16: ...Preparing the Installation 7 Front cover removed ...
Page 45: ...Installing the Inverter 36 IP66 0 4 0 8kW 3 phase 1 5 2 2kW 3 phase ...
Page 50: ...Installing the Inverter 41 0 4 22kW Standard I O Multiple I O ...
Page 67: ...Installing the Inverter 58 ...
Page 69: ...Learning to Perform Basic Operations 60 30 75kW Models ...
Page 193: ...Table of Functions 184 ...
Page 205: ...196 Troubleshooting ...
Page 228: ...Technical Specification 219 30 75kW Models 30 kW 3 Phase 37 45 kW 3 Phase ...
Page 230: ...Technical Specification 221 IP66 Models 0 4 4 0kW NP Non PDS type ...
Page 231: ...Technical Specification 222 0 4 4 0kW PDS type ...
Page 233: ...Technical Specification 224 5 5 7 5kW NP Non PDS type ...
Page 235: ...Technical Specification 226 11 0 22 0kW NP Non PDS type ...
Page 259: ...250 ...
Page 261: ...252 ...
Page 263: ...254 ...