Technical Specification
203
7
Technical Specification
7.1
Input and Output Specification
0.4-22kW Models
Single Phase 200V (0.4-2.2 kW)
Model
□□□□
S100
–
1
□□□□□
0004
0008
0015
0022
Applied
motor
Heavy load
HP
0.5
1.0
2.0
3.0
kW
0.4
0.75
1.5
2.2
Normal
load
HP
1.0
2.0
3.0
5.0
kW
0.75
1.5
2.2
3.7
Rated
output
Rated
capacity
(kVA)
Heavy load
1.0
1.9
3.0
4.2
Normal
load
1.2
2.3
3.8
4.6
Rated
current (A)
Heavy load
2.5
5.0
8.0
11.0
Normal
load
3.1
6.0
9.6
12.0
Output frequency
0-400 Hz (IM Sensorless: 0-120 Hz)
Output voltage (V)
3-phase 200-240 V
Rated input
Working voltage (V)
Single phase 200-240 V AC (-15% to +10%)
Input frequency
50-60 Hz (
±
5%)
Rated
current (A)
Heavy load
4.4
9.3
15.6
21.7
Normal
load
5.8
11.7
19.7
24.0
Weight
(lb/kg)
Non-EMC Filter Type
2.0/0.9
2.9/1.3
3.3/1.5
4.4/2.0
EMC Filter Type
2.5/1.1
3.4/1.6
3.9/1.8
4.9/2.2
IP66 Type(EMC)
8.2/3.7
11.7/5.3
12.1/5.5
12.4/5.6
IP66 Type(Non-EMC)
7.9/3.6
11.5/5.2
11.9/5.4
12.1/5.5
•
The standard motor capacity is based on a standard 4-pole motor.
•
The standard used for 200 V inverters is based on a 220 V supply voltage, and for
400V inverters is based on a 440 V supply voltage.
•
The rated output current is limited based on the carrier frequency set at Cn.04.
•
The output voltage becomes 20~40% lower during no-load operations to protect the
inverter from the impact of the motor closing and opening (0.4-4.0kW models only).
•
IP66 models do not support normal load operation.
Summary of Contents for LSLV-S100 Series
Page 1: ......
Page 11: ...Preparing the Installation 2 ...
Page 13: ...Preparing the Installation 4 5 5 22kW 3 Phase ...
Page 16: ...Preparing the Installation 7 Front cover removed ...
Page 45: ...Installing the Inverter 36 IP66 0 4 0 8kW 3 phase 1 5 2 2kW 3 phase ...
Page 50: ...Installing the Inverter 41 0 4 22kW Standard I O Multiple I O ...
Page 67: ...Installing the Inverter 58 ...
Page 69: ...Learning to Perform Basic Operations 60 30 75kW Models ...
Page 193: ...Table of Functions 184 ...
Page 205: ...196 Troubleshooting ...
Page 228: ...Technical Specification 219 30 75kW Models 30 kW 3 Phase 37 45 kW 3 Phase ...
Page 230: ...Technical Specification 221 IP66 Models 0 4 4 0kW NP Non PDS type ...
Page 231: ...Technical Specification 222 0 4 4 0kW PDS type ...
Page 233: ...Technical Specification 224 5 5 7 5kW NP Non PDS type ...
Page 235: ...Technical Specification 226 11 0 22 0kW NP Non PDS type ...
Page 259: ...250 ...
Page 261: ...252 ...
Page 263: ...254 ...