Chapter 5 Frame Editor
5-23
5.2.3 Frame writing/reading
Basic parameters and frame set by using Frame Editor can be written (downloaded) to Cnet I/F module or read
(uploaded) from Cnet I/F module.
1) Writing (download)
A) First, connect GMWIN cable to COM terminal of PLC CPU module equipped on Cnet I/F module. PC and
COM terminal of PLC shall be connected.
[Figure 5.11] Connection diagram of GMWIN cable
B) Select [Online]-[Connect] in Frame Editor and connect to CPU to display connection completed message.
[Note1]
Remark
[Note1] Online connection via Frame Editor is unavailable if GMWIN program is connected. If GMWIN
program is in service, try the connection after GMWIN is disconnected surely switch PLC CPU over
to STOP before basic parameters or frame is downloaded. If downloaded in PLC run mode, writing
error may occur.
C) Select [Online]-[Write] in Frame Editor to display the dialog box as below.
Cable connection of RS-232C