Appendix
A-10
Error code
Error type
Contents
Action to take
4201
4202
4203
4204
Operation mode change error
4201: Present operation mode RUN
4202: Present operation mode STOP
4203: Present operation mode PAUSE
4204: Present operation mode Debug
Execute again with changeable
operation mode.
(indicated in Cnet V1.5 or later)
4142
Download initialization error
When downloading with Domain not
deleted
Check if Domain deleted or not.
Set remote control by PLC basic
parameter communication in
GMWIN to allowed, and then
execute again.
4200
Domain Delete impossible
When executing Domain Delete with
PI not deleted
Delete PI and then execute again.
4242
Upload initialization error
* Domain not downloaded
* Domain name mismatch
Check if Domain deleted or not
Execute again after checking
domain name.
4342
Down/upload sequence error
Frame number mismatch
Execute again from beginning
after adjusting frame number.
4442
Down/upload initialization
error
Initialization command not executed
Execute again down/upload after
executing initialization command.
0090
Monitor execution error
Registration number of appropriate
monitor not registered.
Execute again after registering
monitor.
0190
Monitor execution error
Registered number exceeding range
Execute again after adjusting
monitor registration number to 31
or less.
0290
Monitor registration error
Registered number exceeding range.
Execute again after adjusting
monitor registration number to 31
or less.
No
response.
No response
* Station No. error/ BCC error
* Main command/command type error
* Header and tail character error
* Cable error
* Operation mode error.
* Communication speed/stop/data/
parity bit error.
* PLC error.
Check and take actions for error
contents that may occur.